Accessories
4.5 Manual operators
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
279
Locking at the masking plate of the panel door with cylinder lock (Kaba)
The door mounted rotary operator can be locked at the panel door with a cylinder lock (type
Kaba).
The cylinder lock can not be used for locking in the ON (I) position.
Note
The cylinder lock (type Kaba) for the masking plate must be ordered separately.
Locking, blocking and interlocking at the rotary operator
Locking at the rotary operator is possible with up to three padlocks with a diameter of
3/16" - 5/16" / 5 - 8 mm and with a cylinder lock (type Ronis). Interlocking is only possible
with cylinder locks (type Ronis).
In addition, the door mounted rotary drive can be locked at the masking plate in the panel
door additionally with cylinder locks (type Kaba).
Padlocks and cylinder locks are not included in the scope of supply of manual rotary
operators.
Locking with padlocks
All rotary operators have a mechanism for padlocks. This can be pulled out from the rotary
operator.