Connecting a redundant power supply to 1 power supply unit
Use the terminal block "X1" to connect the power supply.
X1
F2
F1
M2 L2
M1
L1
L2
L1
Figure 6-2
Assignment of the LED display to the pins for redundant power supply with devices with one
power supply unit
X1
F2
F1
M2 L2
M1
L1
F2
F1
M2 L2
M1
L1
L2
L1
X2
Figure 6-3
Assignment of the LED display to the pins for redundant power supply with devices with two
power supply units
● If the power supply fails at pins L1/M1, this is indicated by LED L1.
● If the power supply fails at pins L2/M2, this is indicated by LED L2.
Connecting a redundant power supply to 2 power supply units
To connect the power supplies, use pins L1/M1 of the left terminal block "X1" and pins L1/M1
of the right terminal block "X2". Only "L1" is monitored on each terminal block.
Since both power supply units have connectors for redundant power supply, you can connect
2 power supplies to each of the two power supply units. This should, however, only be
necessary in extremely rare situations.
Connecting
6.7 Power supply
SCALANCE X-300EEC
Compact Operating Instructions, 11/2019, A5E02630809-14
53