instabus EIB
Technical Product Information
August 2005
Socket outlet switch wave S 564
5WG3 564-7AB11
Siemens AG
S 564, 4 pages
Technical Manual
Automation and Drives Group
Electrical Installation Technology
©
Siemens AG 2005
Update: http://www.siemens.de/gamma
P.O. Box 10 09 53, D-93009 Regensburg
Subject to change without prior notice
2.20.7.1/3
Commissioning:
The connection e.g. of a push button wave with the
socket outlet switch wave is carried out by pressing the
push button of the push button wave and the push but-
ton of the socket outlet switch wave. To do so, the spe-
cial function must be set for the two devices which have
to be connected with each other. The operating state
and the successful connection are displayed by the
LEDs of both devices.
Connection via radio control:
Connecting a push button wave to a socket outlet switch
wave via radio control:
B1
B2
Figure 3:
B1 push button wave
B2 socket outlet switch wave
1. Socket outlet switch wave: Switch to special func-
tion (B2)
Action: Press the push button for at least 10 seconds.
Display: The LED begins to flash slowly (approx. once
per second) after 10 seconds (switches to special
function).
2. Push button wave: Switch to special function (B1)
Action: Press the push button rocker in the CENTRE for
at least 10 seconds.
Display: The LED of the push button begins to flash
slowly (approx. once per second) after 10 sec-
onds (toggling to the special function).
.
3. Push button wave: Transmit a linking telegram (B1)
Action: Brief operation (up to 0.4 sec.) of the push button
rocker at the TOP, CENTRE or BOTTOM.
Display: The LED of the push button wave flashes rapidly
(3 times per sec.) for approx. 3 seconds if the con-
nection has been established successfully. The
LED is then extinguished and the push button ex-
its the special function. The LED of the socket out-
let switch wave flashes in the same way and the
special function mode is terminated.
Note:
There is only a limited period available for the
connection as both devices exit the special function after
2 minutes.
The connection of the socket outlet switch wave with the
push button wave is complete. When the push button
wave is operated the socket outlet switch wave will be
switched as well via the radio connection.
If the connection has failed (e.g. if the distance is too
great), both devices exit the special function after
approx. 2 minutes, without confirming the success of the
connection by flashing rapidly.
This procedure must be repeated if the socket outlet
switch is to be connected with other push buttons or
sensors (up to 10 connections possible).
Procedure for deleting a connection:
Single connections can be deleted by reconnecting an
already known device.
Deletion of the connection between a push button wave
and the socket outlet switch wave:
1.
Socket outlet switch wave: Switch to the special func-
tion
2.
Push button wave: Switch to the special function
3.
Push button wave: Trigger a linking telegram
The connection between the socket outlet switch wave
and the push button wave is thereby deleted.
Deleting all connections and resetting to the sup-
plied state:
1.
Switch the push button wave to the special function.
Action: Press the push button for at least 10 seconds.
Display: The LED begins to flash slowly (approx. once
per second) after 10 seconds (switches to the
special function).
2.
Reset the device
Action: Press the push button again for at least 10 sec-
onds.
Display: The LED of the push button flashes rapidly (3
times per second) for approx. 3 seconds. The
LED is then extinguished and the socket outlet
switch wave exits the special function.
All connections in this device are deleted. The device is
restored to its initial state.
Connections to the socket outlet switch wave in other