Heating controllers RVP201 and RVP211
CE1P2464en
Building Technologies
3 Technical design
2017-07-21
3 Technical
design
3.1 Operating
modes
The
RVP211
provides the following operating modes:
Automatic operation normal / protection mode
Automatic changeover between normal temperature and protection mode
according to the 24-hour or weekly program
Automatic d.h.w. heating
Load-dependent switching on and off of the heating in function of the
outside temperature while giving consideration to the building’s thermal
inertia (ECO automatic energy saver)
Optional remote operation with the help of a room unit
Frost protection is ensured
Automatic operation normal / reduced
Automatic changeover between normal and reduced temperature accord-
ing to the 24-hour or weekly program
Automatic d.h.w. heating
Load-dependent switching on and off of the heating in function of the
outside temperature while giving consideration to the building’s thermal
inertia (ECO automatic energy saver)
Optional remote operation with the help of a room unit
Frost protection is ensured
Setback mode
Continuous heating to the reduced temperature
Automatic d.h.w. heating
Load-dependent switching on and off of the heating in function of the
outside temperature while giving consideration to the building’s thermal
inertia (ECO automatic energy saver)
Frost protection is ensured
Normal mode
Continuous heating to the normal temperature
Automatic d.h.w. heating
No ECO automatic energy saver
Frost protection is ensured
D.h.w. heating only
Automatic d.h.w. heating
Control of heating to protection mode
Frost protection is ensured
Protection mode
Heating to the frost protection level
Frost protection is ensured
Manual operation
No control
Heating circuit pump runs
Control with seat or slipper valve: relay de-energized
Control with burner: boiler always ON
D.h.w. charging pump runs or d.h.w. changeover valve is deactivated
The
RVP201
does not provide
“d.h.w. heating only”.