RUGGEDCOM RS900W
Installation Guide
Chapter 6
Certification
RoHS
31
Section 6.1.5
RoHS
This device is declared by Siemens Canada Ltd to meet the requirements of the following RoHS (Restriction of
Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic
equipment:
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Information Products
A copy of the Material Declaration is available online at
https://support.industry.siemens.com/cs/ww/en/
Section 6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS900W has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
x
Signal Ports
± 4 kV @ 2.5 kHz
x
DC Power Ports
± 4 kV
4
AC Power Ports
± 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV
4
IEC 61000-4-5
Surge
Signal Ports
± 4 kV Line-to-Ground
± 2 kV
4