![Siemens RUGGEDCOM RS400 Installation Manual Download Page 46](http://html.mh-extra.com/html/siemens/ruggedcom-rs400/ruggedcom-rs400_installation-manual_377335046.webp)
Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severi-
ty Lev-
els
DC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
AC Power Ports
2.5 kV common, 1 kV dif-
ferential mode at 1 MHz
3
Signal Ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-16
Mains Frequen-
cy Voltage
DC Power Ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
Signal Ports
2 kVac (Fail-Safe Relay Output)
DC Power Ports
1.5 kVDC
Dielectric
Strength
AC Power Ports
2 kVAC
Signal Ports
5 kV (Fail-Safe Relay output)
DC Power Ports
5 kV
IEC 60255-5
H.V. Impulse
AC Power Ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS400 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
±8 kV
ESD
Enclosure Air
±15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
±4 kV at 2.5 kHz
DC Power Ports
±4 kV
AC Power Ports
±4 kV
Fast Transient
Earth Ground Ports
±4 kV
Signal Ports
2.5 kV Common Mode at 1 MHz
DC Power Ports
1 kV Common and Differential Mode at 1 MHz
Oscillatory
AC Power Ports
1 kV Common and Differential Mode at 1 MHz
Signal Ports
2 kVAC
DC Power Ports
1.5 kVDC
Dielectric Strength
AC Power Ports
2 kVAC
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
RUGGEDCOM RS400
Installation Manual, 02/2020, C79000-G8976-1016-10
37