Technical Guidance Notes
Page 26 of 29
©2007 Siemens Protection Devices Limited
Figure 27 – RMC30 Browser Interface – IED DNP3 Device Entry
That completes configuration for the RMC30 in DNP3 mode, click
Log Out
. Connection can be made
to the IP address using the default DNP3 client port number of 20000. If you need to change this
parameter open the Configure Protocols branch,
see Figure 17 – RMC30 Browser Interface – Serial
Protocols Menu
, select DNP client and change the IP Port number.
3.4 C
ONFIGURE
RMC30
T
UNNEL
P
ARAMETERS
If you have not already done so, set the IP address as described in section
3.1.
After setting the IP address start the web browser and login. From the Main Menu open the Serial
Protocols page, refer back to
Figure 17 – RMC30 Browser Interface – Serial Protocols Menu
. Then
click Serial ports. Set the protocol to be Raw Socket and the baud rate to be those you intend to use
with the relay, see example shown below in Figure 28.
Figure 28 – RMC30 Browser Interface – Serial Port for Raw Socket
That completes configuration for the RMC30 in Tunnel mode, click
Log Out
. In this mode you do not
need to add any devices to the Device Table. Connection can be made to the IP address using the
default Raw Socket client port number of 50001. If you need to change this parameter open the
Configure Protocols branch,
see Figure 17 – RMC30 Browser Interface – Serial Protocols Menu
,
select Raw Socket and change the Loc Port number.