RUGGEDCOM RMC30
Installation Guide
Chapter 3
Communication Ports
Serial Terminal
15
Section 3.2
Serial Terminal
The RUGGEDCOM RMC30 is equipped with a seven-terminal Phoenix-style connector. This connector can
accommodate one RS232 connection, and one RS485/422 connection. The following is the pin-out for the serial
terminal:
1
7
Figure 8: Serial Terminal Pin Configuration
Pin
Name
Mode
Description
1
Rx
RS232
Receive data
2
Tx
RS232
Transmit data
3
COM
Shared common
4
-Rx
RS422/485
Receive data-
5
+Rx
RS422/485
Receive data+
6
-Tx
RS485
Transmit data-
7
+Tx
RS485
Transmit data+
CONTENTS
•
Section 3.2.1, “RS232 Data Ports”
•
Section 3.2.2, “RS485/422 Data Ports”
Section 3.2.1
RS232 Data Ports
The serial terminal includes a single EIA/TIA RS232 compliant port, consisting of three terminals: Transmit (Tx),
Receive (Rx) and Common (COM).
IMPORTANT!
The RS232 port is intended for point-to-point applications only.
In adherence to the EIA/TIA guidelines for RS232 communications, the following is recommended by Siemens:
• Always use shielded cabling to minimize the effects of ambient electrical noise
• Although greater distances are possible, limit the cable length to 15 m (49 ft) or less for more reliable
communications
• Use a baud rate of 120 kbps
The RS232 port uses a Phoenix-style DB9 compression connector. The following is the pin-out for the connector:
Summary of Contents for RUGGEDCOM RMC30
Page 4: ...RUGGEDCOM RMC30 Installation Guide iv ...
Page 12: ...Chapter 1 Introduction RUGGEDCOM RMC30 Installation Guide 4 Description ...
Page 20: ...Chapter 2 Installing the Device RUGGEDCOM RMC30 Installation Guide 12 Resetting the Device ...
Page 26: ...Chapter 3 Communication Ports RUGGEDCOM RMC30 Installation Guide 18 RS485 422 Data Ports ...