Siemens RPT Installation Instructions Download Page 2

Document No. 540-369 
Installation Instructions  
December 15, 2004 

Instructions 

1.  Verify that the electrical box, onto which the front 

part of the RPT will be mounted, is grounded. 

NOTE: 

In Steps 2 through 5, you will determine 
where, on the outside wall, to drill a 2-
inch hole. You will use the outside 
cover plate on the inside wall to make 
offset measurements from the door 
frame to the air inlet and then transfer 
these measurements to the outside 
wall. 

2.  Temporarily mount the 

outside

 cover plate onto 

the electrical box in the 

inside

 wall, with the 

outside

 cover plate oriented so that the Siemens 

Building Technologies logo is at the bottom. 

 

CAUTION: 

 

For the RPT to function properly, the 
airflow tube that connects the front and 
rear cover plates must be level. Since the 
next two steps determine the location of 
the rear cover plate on the outside wall, 
they are critical to the accurate operation 
of the RPT. 

3.  On the inside wall, measure the distances from 

the middle hole in the outside cover plate’s air 
inlet to the floor and the door frame, as shown in 
Figure 2, and then remove the outside cover 
plate from the inside wall. 

 

CAUTION: 

 

If the floors inside and outside the room 
are at a different level, be sure to account 
for 

this

 difference in Step 4. 

NOTE: 

The location indicated in Figure 2 is the 
CDC’s (Center for Disease Control) 
recommended mounting location. If the 
specified mounting location is not 
feasable, select another location 
approved by the owner.  

6-18"

(15.25 - 45.7cm)

6-18"

(15.25 - 45.7cm)

NOTE: POSITION SO THAT

SIEMENS LOGO IS AT 

THE BOTTOM

(UPSIDE DOWN)

SEN0180R2

S

 

Figure 2.  Measuring Distances on Inside Wall. 

4.  On the outside wall, mark off the distances from 

the floor and the doorframe and locate the point 
of intersection. 

5.  At the intersection point, drill a 2-inch diameter 

hole in the outside wall. Take care to use the 
intersection point as the exact center to ensure 
the new hole will be completely concealed by 
the outside cover plate. 

6.  Be sure the airflow tube is clear of debris and 

then press it onto the black plastic mount on the 
RPT circuit board, as far as it will go. 

7.  Temporarily attach the inside cover assembly to 

the inside wall (oriented with the Siemens 
Building Technologies logo at the top) and make 
a pencil mark on the airflow tube where it exits 
the outside wall. Then remove the inside cover 
plate assembly from the inside wall. 

8.  Cut off the length of tubing that extends beyond 

the pencil mark, and then remove any burrs from 
the end of the tube. Place the rubber section of 
the tubing on the newly cut end. 

NOTE: 

Tubing runs longer than 12 inches will 
degrade the signal and cause poor 
performance. Do not use tubing longer 
than the tubing provided.  

9.  Connect the pressure signal cable to terminals 

1(

+

, Hot) and 3(

, Common) of the 3-pin 

terminal block, then plug it into the receptacle on 
the RPT (see Figure 3). 

Page 2 of 3 

Siemens Building Technologies, Inc. 