Siemens Industry, Inc.
Building Technologies Division
P/N 315-033420-13
2
Figure 2
Connecting The 24VDC Input
Figure 3
Connecting HNET/XNET At The End Of The Network (Style 4 and Style 7)
(HNET PMI/PMI-2/PMI-3 Only For Style 7)
NOTES:
1. 14-18 AWG.
2. 2A max. input current.
3. Supervised
4. Refer to PSC-12/PSX-12
Installation Instructions,
P/N 315-033060 for
connection to TB3 and
ground fault detection
impedance.
NOTES:
1. No EOLR required.
2. 18 AWG min., 14 AWG max.
3. 2000 feet max. per pair.
4. Use twisted pair (Style 4/7)
or twisted shielded pair
(Style 4 only).
5. Power limited to NFPA 70
per NEC 760.
6. Refer to NIC-C Installation
Instructions, P/N 315-
033240 for connection of
A and B pairs and ground
fault detection impedance.
7. Omit B pair for Style 4.
8. All wiring supervised.
24
V
+
+
–
–
S
3
2
1
TB1
RNI
TO PSC-12 TB3
OR ANY UL/ULC
REGULATED,
POWER LIMITED
POWER SUPPLY
LISTED FOR FIRE
PROTECTIVE
SIGNALING USE
SHIELD
1
A–
A–
2
A+
A+
3
S
4
B–
B–
5
B+
B+
6
S
TB2
RNI
FROM
NIC-C
SHIELD
SET TO ON
PRESS
DOWN
SHIELD
S1
PRE-INSTALLATION
P7 enables or disables an audible device similar to the CSB. This audible sounds
whenever a switch is pressed on either the LVM, SCM-8 or the FCM-6. If this is not
desired the audible can be silenced by changing the jumper installed on P7 to
positions 2 and 3. P7 is configured in the factory (positions 1 and 2) to have the
audible active.
S1 is used to terminate the HNET/XNET. If the RNI is installed at the end of an HNET
network, S1 must be set to the ON position. If the RNI is in the middle of the HNET/
XNET, set S1 to the OFF position.
P5 must be set to the HNET (H) position to select HNET or the XNET (X) position to
select XNET. Only one network, either HNET or XNET, can be used.
INSTALLATION
Remove all system power before installation, first battery then AC. (To power up,
connect the AC first, then the battery.)