6 / 10
Siemens
Universal Modules
CE1N3146en
Building Technologies
2016-03-10
Power supply external
Voltage
AC 24 V
devices (G1)
Current
max. 4 A
Electrical connections
Connection terminals
spring cage terminals
For solid wires
0.6 mm dia.…2.5 mm
2
For stranded wires without ferules
0.25…2.5 mm
2
For stranded wires with ferules
0.25…1.5 mm
2
Protection
Degree of protection of housing to IEC 60 529
IP20 (when mounted)
Safety class to EN 60 730
device suited for use with
equipment of safety class II
Environmental conditions
Operation to
IEC 60 721-3-3
Climatic conditions
class 3K5
Temperature (housing with electronics)
0…50 °C
Humidity
5…95 % r.h. (noncondensing)
Mechanical conditions
class 3M2
Transport to
IEC 60 721-3-2
Climatic conditions
class 2K3
Temperature
25… 70 °C
Humidity
<95 % r.h.
Mechanical conditions
class 2M2
Classifications to
Mode of operation, automatic controls
type 1B
EN 60 730
Degree of contamination, controls environment
2
Software class
A
Rated surge voltage
4000 V
Temperature for ball-test of housing
125 °C
Materials and colors
Terminal base
Polycarbonate, RAL 7035 (light-
grey)
Insert
Polycarbonate, RAL 7035 (light-
grey)
Packaging
corrugated cardboard