Inrush Response Test
Test conditions
17
Simulated inrush current with 15 % 2
nd
harmonic content
Test result
17
The immunity against inrush currents is up to 3 times the peak value
with 95 % fundamental current (I
set
).
4.12
17
Applicable for 7SR450[1/3]-xGA10-1AA0 variants