Do you want to reload the default timer settings? 

 

 

+

 

 

1. 

Set the controller to protection mode 

.

 

 

 

2. 

Press 

 and 

 simultaneously for 3 seconds. Release them and, within 2 

seconds, press 2 times 

.

 

Day/s 

Time when controller is in normal operation 

 

Mo (1) – Fr (5) 

06:30 – 08:30 (A1) 

17:30 – 22:30 (A2) 

Sa (6) 

08:00 – 23:00 (A3) 

Su (7) 

08:00 – 22:30 (A4) 

Default 

settings 

 

 - in the remaining time controller is in energy saving   
 - timer A5…A8 are free, no default setting 

Changing the control parameters 

To optimize the control performance, a number of control parameters can be adjusted. This can 
also be made during operation without opening the controller. 
If you want to change the control parameters, proceed as follows: 
(For factory settings, see table on the right-hand side) 

 

+

 / 

 

 

   

 
 
 

 

+

 

 

   

 

+

 

 

 

 

1.  Set the controller to protection mode 

 

2. Press   and 

 simultaneously for a minimum of 3 and a  

maximum of 5 seconds. Release them and, within 2 seconds, press  
the 

 again for 3 seconds. The display will show “P01”. 

3.  Select the required parameter by repeatedly pressing the 

 or 

 button: 

P01

P02

P18

+

-

+

-

+

3075Z03

+

-

 

4. By 

pressing   and 

 simultaneously, or by pressing 

, the current  

value of the selected parameter appears, which can be changed by repeatedly 
pressing 

 or 

5.  5 seconds after the last press of a button, or by pressing 

 and 

  

simultaneously, the value will be stored.  

6.  If you wish to display and change additional parameters,  

repeat steps 3 through 5. 

7.  10 seconds after the last display or setting, all changes are  

stored and the controller will return to standby. 

8. 

Switch to comfort operation 

 with the 

 

 

 

  button.

 

Changing the batteries 

 

 

1. 

Get 2 new batteries of type AA alkaline, 1.5 volts. 

 

2. 

Within 1 minute: Remove the battery holder, then the batteries, insert new batteries and replace the battery holder. 

 

3. 

Make certain the old batteries are disposed of properly, in compliance with environmental requirements.

 

Recalibrating the sensor 

If the room temperature displayed by the controller does not agree with the temperature effectively measured, the temperature sensor can be 
recalibrated. For that purpose parameter P07 must be changed.

 

 

Proceed as described under “Changing the control parameters” and follow steps 1 through 3 to select parameter P07. 
With step 4, the room temperature displayed can now be matched to the temperature effectively measured. Each push of the 

 or 

 

button changes the temperature by + or – 0.5 °C up to a maximum of + / - 3 °C. With step 7, the recalibration is automatically stored 10 
seconds after the last readjustment. 

 

Commissioning (by qualified HVAC staff)

 

(all temperature settings can be made in increments of 0.5 K and the time in increments of 1 min.)

 

 

Para-
meter

Controller’s parameter factory settings: 

 

Setting range , step 

RDX33 

RDX43 

P01  Setpoint of heating in energy saving mode 

(W heat 

Eco

16 

OFF, 5 °C…W cool 

Eco

, 0.5 K 

 

 

P02  Setpoint of cooling in energy saving mode 

(W cool 

Eco

28 

OFF, W heat 

Eco

…40 °C, 0.5 K 

 

 

P03*  Setpoint of heating in protection mode 

 (W heat 

PROT

8 °C 

OFF, 5 °C…W cool 

PROT

,

 

0.5 K 

 

 

P04*  Setpoint of cooling in protection mode 

 (W cool 

PROT

OFF 

OFF, W heat 

PROT

 …40 °C, 0.5 K 

 

 

P05  Min. setpoint limitation in Comfort mode   (W min 

Comf.

5 °C 

5…40 °C, 0.5 K 

 

 

P06  Max. setpoint limitation in Comfort mode   (W max 

Comf.

35 °C 

5…40 °C, 0.5 K 

 

 

P07 Sensor 

calibration 

0 K 

-3…+3 K, 0.5 K 

 

 

P08  Switching differential heating SDH 

2 K 

0.5…+4K, 0.5 K 

 

 

P09  Switching differential cooling SDC 

1 K 

0.5…+4K, 0.5 K 

 

 

P10  Setpoint differential between heating & auxiliary heating W

D

 

2 K 

0.5…+5K, 0.5 K 

 

P11  Minimum compressor on-time (Q14) 

1 min. 

1…10 minutes, 1 min. 

 

 

P12  Minimum compressor off-time (Q14) 

3 min. 

1…10 minutes, 1 min. 

 

 

P13  Auxiliary heater minimum hold-time 

1 min. 

1…10 minutes, 1 min. 

 

P14  Selection of °C or °F 

°C 

C or °F 

 

 

P15  Display of temperature or setpoint 

ON 

OFF: Setpoint 
ON: Room temperature 

 

 

P16  Auxiliary heater in heating mode 

1: Enable

0: Disable 
1: Enable 

 

P17  Time format option 

1: 24 h 

0: 12 hour format 
1: 24 hour format 

 

 

P18  Operating action changeover heating/cooling Q21 - Q22 

0:  

0: Open (heating), close 
(cooling) 
1: Close (heating), open 
(cooling) 

 

 

Legend to table 

 

Adjustable: Please record all changes you make

 

 

 

Not adjustable / display only

 

 X 

Not available 

P03* / P04*: 

P04 is at least min. 5 K higher than P03 

Energy saving tips without sacrificing comfort 

 

Never allow room temperatures to exceed 21

˚

C.  

 

Air out rooms for short periods of time only, but properly, with the windows wide open. 

 

Do you want to view the programmable timer settings?

 

 