2019-10-25
Control parameters
To optimize the control performance, you can use local HMI to adjust a number of
control parameters. Proceed as follows to change the control parameter.
1.
Set the thermostat to Protection mode
.
2.
Press and hold the
+
and
–
buttons simultaneously for 3 seconds. Release them
and, within 2 seconds, press and hold the
+
button again for 3 seconds. Then,
P03
displays.
3.
Select the required parameter by pressing the
+
and
–
buttons:
4.
Press the
+
and
–
buttons simultaneously. Te current value of the selected
parameter displays on the screen. Press the
+
or
–
button to change the value.
5.
You can either press the
+
and
–
buttons simultaneously to confirm the change
or wait for 5 seconds to have the change saved automatically.
6.
Repeat steps 3 through 5 to change more parameters.
7.
10 seconds after the last display or setting, all changes are saved and the
thermostat returns to Protection mode.
Reload the factory setting of the control parameters as follows:
1.
Set the thermostat to Protection mode
.
2.
Press the
+
and
–
buttons simultaneously for 3 seconds. Release them and,
within 2 seconds, press the
button twice.
Then
888
displays during the reloading process.
Para-
meter
Meaning
Setting range
Factory
setting
P03
Setpoint of heating in Protection Mode
(Wheat
Stb
)
OFF, 5 °C…Wcool
Stb
8 °C
P04
Setpoint of cooling in Protection Mode
(Wcool
Stb
)
OFF, Wheat
Stb
…40 °C
OFF
P05
Minimum setpoint limitation in Comfort Mode
(Wmin
Norm
)
5 °C…Wmax
Norm
5 °C
P06
Maximum setpoint limitation in Comfort Mode
(Wmax
Norm
f
)
Wmin
Norm
…40 °C
35 °C
P07
Sensor calibration
-3…3 K
0 K
P08
Switching differential heating mode SDH
0.5…4 K
1 K
P09
Switching differential cooling mode SDC
0.5…4 K
1 K
P14
Dwelling time of auto fan speeds
1…5 min
2 min
P17
Selection of °C or °F
°C or °F
°C
P18
Display of temperature or setpoint
OFF: Setpoint
ON: Room (or return air) temperature
ON
P21
Fan control in Comfort mode
OFF in dead zone
ON in dead zone
ON
P22
Heating/cooling mode
0: Heating only
1: Cooling only
3: Manual H/C changeover
3: Manual
Parameter settings
Parameter reset
Control parameters