Warning notes 

To avoid injury to persons, damage to property or the environment, the following 
warning notes must be observed! 
 
Do not open, interfere with or modify the flame detector! 

 

 

All activities (mounting, installation and service work, etc.) must be performed by 
qualified staff 

 

Before making any wiring changes in the connection area, completely isolate the 
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be 
inadvertently switched on again and that it is indeed dead. If not observed, there is 
a risk of electric shock hazard 

 

Ensure protection against electric shock hazard by providing adequate protection 
for the connection terminals. If this is not observed, there is a risk of electric shock 

 

Each time work has been carried out (mounting, installation, service work, etc.), 
check to ensure that wiring is in an orderly state. 

If this is not observed, there is a 

risk of loss of safety functions and a risk of electric shock

 

 

Fall or shock can adversely affect the safety functions. Such flame detectors or 
burner controls must not be put into operation, even if they do not exhibit any dam-
age. 

If this is not observed, there is a risk of loss of safety functions and a risk 

of electric shock

 

Mounting notes 

 

Ensure that the relevant national safety regulations are complied with 

 

The flame detector plugs into the burner (the detector’s clamp engages on the 
burner’s light metal flange) 

Installation notes 

 

Always run the high-voltage ignition cables separate from the unit and other cables 
while observing the greatest possible distances 

Electrical connection of the flame detector 

It is important to achieve practically disturbance- and loss-free signal transmission: 

 

Never run the detector cable together with other cables 
– Line capacitance reduces the magnitude of the flame signal 
– Use a separate cable 

 

Observe the permissible detector cable lengths (refer to 

Type summary

 and 

Tech-

nical Data

 

Summary of Contents for RAR Series

Page 1: ...e used especially in connection with burner controls for the control and supervision of large capacity burners The RAR and this Data Sheet are intended for use by OEMs which integrate the flame detectors in their products Use The RAR flame detectors are used for the supervision of yellow burning oil flames They are designed for use with the following types of burner controls LAL LAE1 LAE10 LOK16 L...

Page 2: ...is in an orderly state If this is not observed there is a risk of loss of safety functions and a risk of electric shock Fall or shock can adversely affect the safety functions Such flame detectors or burner controls must not be put into operation even if they do not exhibit any dam age If this is not observed there is a risk of loss of safety functions and a risk of electric shock Mounting notes E...

Page 3: ...ISO 9001 2008 ISO 14001 2004 OHSAS 18001 2007 China RoHS Hazardous substances table http www siemens com download A6V10883536 Service notes Each time a unit has been replaced check to ensure that wiring is in an orderly state and that the wires are firmly connected Disposal notes The flame detector contains electrical and electronic components and must not be dis posed of together with household w...

Page 4: ...lange with radius Silicon BPZ RAR9 2 RAR9 2 Max 100 m With clamp and flange straight Silicon The information in the data sheet for the relevant burner control also apply When ordering please give the type reference according to Type summary Accessories to be ordered separately Item Part number Flange with radius 4 241 8855 0 Flange straight 4 241 8898 0 Clamp 4 199 8806 0 Type reference Descriptio...

Page 5: ...ature range 20 60 C Humidity 95 r h Operation DIN EN 60 721 3 3 Climatic conditions class 3K5 Mechanical conditions class 3M2 Temperature range 20 60 C Humidity 95 r h Installation altitude Max 2 000 m above sea level Warning Condensation formation of ice and ingress of water are not permitted If not observed the safety functions are no longer ensured and there will be a risk of electric shock Fun...

Page 6: ... 2 A 4 Ø4 3 2 5 A ca Ø21 Ø 2 2 A A 3 R0 1 1 5 5 8 4 0 2 1 2 7713m02 0716 4 241 8855 0 36 24 3 R0 3 10 R2 7 R2 R4 18 24 48 3 3 15 30 2 5 Company logo to LN 3 8380 0102 0 2 mm elevated 7712m09e 1001 4 241 8898 0 7 2 5 3 36 18 15 30 R4 3 10 24 48 Company logo to LN 3 8380 0102 0 2 mm elevated 7712m10e 1001 Accessories Ordering Information Part No SBRAR9 1 ...

Reviews: