Siemens RAB10 Series Technical Instructions Download Page 2

Technical Instructions 

RAB10 Series Two-pipe Fan Coil Room Thermostat 

Document Number 155-524P25 
March 2, 2007 

Page 2

  

Siemens Industry, Inc. 

 

Operation, 
Continued 

Fan Speed 

The fan control speed can be controlled two ways: 

 

Manually, using the three-speed fan switch on the thermostat cover for continuous 

operation.   (Low), 

 (Medium), 

 (High). 

 

Automatically, by switching to the selected fan speed using the thermostat for 
controlled operation. Prior to commissioning, the jumper position corresponding to 
the thermostat function must be selected.  

Fan Release Setting 

There are two jumper position choices on the printed circuit board: 

 

Jumper SR1   

Selected fan speed as continuous operation 

 

Jumper SR2   

Auto

  

Fan is switched at the same time as the valve 

Ventilation 

When the ventilation function is selected (RAB10.1..), the heating and cooling contacts 
are always open and the fan works at the selected speed. 

Changeover 

The control algorithm can be selected with a switch located on the front of the controller 
(change over switch). 

Adjustments 

The required temperature can be selected by a rotating setpoint adjuster at the front of 
the thermostat. 

High and low setpoint limit stops can be engaged to limit temperature range. 

 

Table 1.  Product Numbers. 

 

Mounting Style 

Product Number 

Description 

Electrical Wall Box 

(with wall box 

adapter) 

RAB10.1UW 

2-pipe; manual changeover; degrees 
Fahrenheit and Celsius; fan only 
function 

Drywall 

RAB10.1U 

2-pipe; manual changeover; degrees 
Fahrenheit and Celsius; fan only 
function 

 

Accessory 

ARG70 Wall Box Adapter 

Warning/Caution Notations 

 

WARNING: 

 

Personal injury, or loss of life may occur if 
you do not perform a procedure as 
specified. 

CAUTION: 

 

Equipment damage, or loss of data may 
occur if you do not follow a procedure as 
specified. 

Summary of Contents for RAB10 Series

Page 1: ...h Two mounting styles electrical wall box or drywall Wall plate adapter ARG70 included with electrical wall box mount styles Application Typically used in commercial high rise and light industrial buildings in conjunction with Zone valves Thermal valves Fans Product Numbers See Table 1 Technical Design The RAB10 fan coil room thermostat is based on a two wire gas diaphragm technology Operation Hea...

Page 2: ...nction is selected RAB10 1 the heating and cooling contacts are always open and the fan works at the selected speed Changeover The control algorithm can be selected with a switch located on the front of the controller change over switch Adjustments The required temperature can be selected by a rotating setpoint adjuster at the front of the thermostat High and low setpoint limit stops can be engage...

Page 3: ...113 1 42 8 mm Color Ivory white with gray selector knobs Ambient Conditions Operation Temperature 32 F to 122 F 0 C to 50 C Relative humidity 95 Transport Storage Temperature 4 F to 122 F 20 C to 50 C Relative humidity 95 Wiring Screw terminals for wires of 2 16 AWG or 1 14 AWG Minimum 20 AWG Housing Material Plastic Enclosure rating NEMA1 Bellows Environmentally friendly gas Agency Certification ...

Page 4: ...unit must be de energized and the operating voltage checked before opening An ARG70 wall plate adapter provided with electrical wall box mount models must be used to mount to a 2 4 inch or 4 4 inch electrical wall box An ARG70 wall plate adapter must be used to meet UL and cUL requirements The thermostat must be mounted on a flat wall All local electrical regulations must be complied with If there...

Page 5: ...vided fasten sub base to wall Thermostat is not position sensitive 10 Pull the wiring through the sub base 11 Position thermostat housing over the two mounting lugs located at the top of the sub base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions on the inside of thermostat cover Optional To set limit stops remove gray tabs located on the setpoin...

Page 6: ...stat cover from the thermostat base and push up to remove cover 3 Using the four screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting S...

Page 7: ...e thermostat cover from the thermostat base and push up to remove cover 3 Using the two screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mou...

Page 8: ...fore servicing Metal part is not grounded Diagrams L Operating voltage M1 3 speed fan N Neutral N1 Room thermostat G1 Control output fan speed I Low G2 Control output fan speed II Medium G3 Control output fan speed III High ZV Zone valve or thermal valve W Y Control output actuator Figure 5 Wiring T Room temperature SD Switching differential SP Room temperature setpoint W Valve output signal heati...

Page 9: ...r company names mentioned herein may be the trademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 524P25 Printed in the USA Pag...

Reviews: