Room Thermostat RAA20 

CE1N3002en 

Building Technologies 

 

25.02.2008 

Notes 

The thermostat should be located where the room temperature can be acquired as 
accurately as possible, without getting adversely affected by direct solar radiation or 
other heat or refrigeration sources. 
Mounting height is about 1.5 m above the floor. 

 

The thermostat can be fitted to most commercially available recessed conduit boxes or 
directly on the wall. 
Only authorized personnel may open the unit to perform service  

(Caution: AC 24…250 V!). 

The unit must be isolated from the mains supply before 

opening. 
When installing the unit, fix the baseplate first, then hook on the thermostat body and 
make the electrical connections. Then, fit the cover and secure it (also refer to separate 
mounting instructions). 
The thermostat must be mounted on a flat wall. 
The local electrical regulations must be complied with. 
If there are thermostatic radiator valves in the reference room, set them to their fully 
open position. 
The room thermostat is maintenance-free. 
The diaphragm is filled with environment-friendly gas. 
The housing is made of plastic. 

Technical data 

Switching capacity 

Voltage 
Current 
Frequency 

 
AC 24...250 V 
0.2…6(2) A 
50 or 60 Hz 

Switching differential SD  

1 K 

Setpoint setting range 

8…30 °C 

Operation 

Climatic conditions 
Temperature 
Humidity 
Pollution degree 

To IEC 721-3-3 
Class 3K5 
0…50 °C 
<95% r.h. 
Normal, to EN 60730 

Transport / storage 

Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

To IEC  721-3-2 
Class 2K3 / 1K3 
-20…50 °C 
<95% r.h. 
Class 2M2 

 conformity 

EC directive on EMC  
Low-voltage directive (LVD) 

 
2004/108/EC 
2006/95/EC  

Product standards 

Automatic electrical controls for  
household and similar use  

 
EN 60730-1 and 
EN 60730-2-9 

Mounting, installation 
and commissioning 

 

Maintenance 
Mechanical design 

 

Operational data 

Environmental conditions 

Norms and standards 

Summary of Contents for raa20 series

Page 1: ...tems to main tain the selected room temperature Typical use Residential buildings Light industrial buildings In conjunction with zone valves or thermal valves gas or oil burners fans pumps Functions The RAA20 room thermostat has separate outputs for heating only and cooling only If the room temperature falls below the selected setpoint the heating contact will close If the room temperature exceeds...

Page 2: ... combinations Description Product no ASN Data sheet Motoric on off actuator SFA21 4863 Thermal actuator for radiator valves STA21 4893 Thermal actuator for small valves 2 5 mm STP21 4878 Accessories Description Product no ASN Adapter plate 120 x 120 mm for 4 x 4 conduit boxes ARG70 Adapter plate 96 x 120 mm for 2 x 4 conduit boxes ARG70 1 Adapter plate for surface wiring 112 x 130 mm ARG70 2 Techn...

Page 3: ...at wall The local electrical regulations must be complied with If there are thermostatic radiator valves in the reference room set them to their fully open position The room thermostat is maintenance free The diaphragm is filled with environment friendly gas The housing is made of plastic Technical data Switching capacity Voltage Current Frequency AC 24 250 V 0 2 6 2 A 50 or 60 Hz Switching differ...

Page 4: ...g RAA200 Color White NCS S 0502 G RAL 9003 Connection diagrams N L D1 N1 Y1 Y2 L T 3001A01 N L N1 Y1 Y2 L D2 T 3001A02 D1 Zone valve or thermal valve for heating D2 Zone valve or thermal valve for cooling L Switching voltage AC 24 250 V N1 Room thermostat Y1 Control output Heat ing AC 24 250 V Y2 Control output Cool ing AC 24 250 V N Neutral conductor T Thermostat element gas filled diaphragm Dime...

Reviews: