RAA Series Room Thermostats
Technical Instructions
Document Number 155-519P25
March 2, 2007
Siemens Industry, Inc.
Page 5
Drywall Mounting
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the thermostat base and push up to
remove cover.
3. Remove sub-base from back of thermostat.
4. Using the sub-base (packed with thermostat) as a template, mark the hole locations
with a pencil.
5. Drill two 1/4-inch diameter holes for plastic wall anchors (provided).
6. Using a mallet, tap in the plastic wall anchors flush with wall.
7. Pull the wiring through the opening in the upper portion of the sub-base.
8. Level the mounting plate.
9. Using the two wood screws provided, fasten sub-base to wall. Thermostat is not
position sensitive.
10. Pull the wiring through the thermostat housing.
11. Position thermostat housing over the two mounting lugs located at the top of the
sub-base, and press down on cover until bottom lugs snap in place.
12. Terminate wires per wiring instructions on the inside of thermostat cover.
Optional:
To set limit stops, remove gray tabs located on the setpoint knob and
position high and low stops around perimeter of knob as required. See Figure 2.
Figure 2. Setpoint Limit Stops.
13. Insert the top of the thermostat cover into the slots located on the top of the
thermostat and press down.
14. Tighten the two screws at the bottom of the thermostat.
The installation is now complete.