Siemens QRI Series Quick Start Manual Download Page 3

3/12

Building Technologies

CC1N7719en

17.07.2018

Installation notes

Locate the detector such that, if possible, only the flickering peripheral range of the
flame will be detected. The view at hot boiler walls or other hot boiler or burner
components must be restricted as much as possible. This can be attained by clearly
confined viewing conditions behind narrow baffle plates. If this is not possible, a viewing
tube should be used to restrict the viewing range to a smaller area of the flame. Length,
diameter and alignment of the viewing tube must be determined through testing,
depending on the size of burner and boiler

The viewing range should be reduced to such an extent that:
a) the minimum detector output signal required is attained over the burner’s entire
    output range (for details, refer to the Basic Documentation of the LMV5... (P7550)
b) after loss of flame, the valve’s operating voltage is switched off by the burner
    control as required by the standards (see

Commissioning notes

).

Electrical connection of the flame detectors

It is important to achieve practically disturbance- and loss-free signal transmission:

·

 

Never run the detector cable together will other cables
- Line capacitance reduces the magnitude of the flame signal
- Use a separate cable

·

 

Observe the permissible length of the detector cables (see

Technical data

)

·

 

Always run the ignition cable separate while observing the greatest possible
distance to other cables (min. 3 cm)

·

 

Test the flame detector on all applications. When used in connection with the
LMV5..., the test is to be made with a test routine (for details, see the Basic
Documentation P7550)

·

 

Make certain that the detector’s cable does not get into contact with hot burner or
boiler surfaces

·

 

Use an AC voltmeter (Ri = 10 M

W

) to ensure that there is no voltage across the

reference line (blue wire =

N

 of the LMV5...) and the burner housing (

PE

)

Commissioning notes

·

 

When commissioning the plant or when doing maintenance work, make the
following safety checks:

Safety check

Anticipated response

a)

Burner startup with flame detector darkened

Lockout at the end of
safety time (TSA)

b)

Burner startup with flame detector exposed to
extraneous light (e.g. light from an incandescent
lamp interrupted at about 20 Hz)

Lockout at the end of
the prepurge time

c)

Simulation of flame failure during operation. For
that purpose, darken the flame detector during
operation and maintain this state

Lockout or restart,
depending on the
burner control’s
configuration

d)

Check the safety time in operation in the event of
loss of flame; for that purpose, disconnect
manually the fuel valves from power and check
the time the burner control requires from this
manual disconnection until the valves’ power
supply is turned off

Burner control
disconnects power
supply to the valves
within the period of time
allowed for the relevant
plant

·

 

Make a loss-of-flame test with the AZL5... of the LMV5... burner control

Summary of Contents for QRI Series

Page 1: ... Detector with infrared sensitive flame detecting element Integrated flame signal amplifier Designed for frontal and lateral 90 illumination Suited for use with burner controls type LMV5 Secured to the burner with flange and clamp The spectral sensitivity of the QRI is a maximum of about 2 µm covering infrared radiation emitted by gas oil and coal flames as well as other sources of infrared light ...

Page 2: ...ence or similar may modulate infrared radiation emitted by hot boiler or burner components in a way that a flame will be simulated Likewise moving parts in the detector s viewing range can cause infrared radiation from the boiler or a viewing tube to be modulated thereby possibly generating sporadic detector signals Strong burner or detector vibrations can also produce variations in radiation For ...

Page 3: ...ignition cable separate while observing the greatest possible distance to other cables min 3 cm Test the flame detector on all applications When used in connection with the LMV5 the test is to be made with a test routine for details see the Basic Documentation P7550 Make certain that the detector s cable does not get into contact with hot burner or boiler surfaces Use an AC voltmeter Ri 10 MW to e...

Page 4: ...n must be observed Mechanical design The QRI has an impact proof housing made of black plastic The lens is fitted in a dust tight position The QRI can be secured to the burner within its adjusting range using the clamp and the flange provided The 3 core connecting cable is ready connected to the QRI and features cable strain relief Depending on the type of burner construction there are flame detec...

Page 5: ...ticle no BPZ AGG2 110 Consisting of heat insulating piece AGG15 14 NPSM thread heat insulation glass adapter sleeve and clamp Adapter protective sleeve Pg9 14 NPSM thread AGG2 120 Article no BPZ AGG2 120 Mounting coupling AGG04 Article no BPZ AGG04 Adapter of 14 NPSM thread for a European pipe thread G1 Heat insulating piece spare part AGG15 Article no BPZ AGG15 Mounting of the mounting coupling A...

Page 6: ...ss 1K3 Mechanical conditions Class 1M2 Temperature range 20 60 C Humidity 95 r h Transport DIN EN 60721 3 2 Climatic conditions Class 2K2 Mechanical conditions Class 2M2 Temperature range 20 60 C Humidity 95 r h Operation DIN EN 60721 3 3 Climatic conditions Class 3K5 Mechanical conditions Class 3M2 Temperature range 20 60 C short time max 1 min up to 75 C Humidity 95 r h Installation altitude Max...

Page 7: ...mpletely be utilized since the frequency and the rate of change of infrared radiation constantly change Hence the detector s ability to capture the flame s radiation behind the burner s baffle plate is extremely high As a result of the high level of sensitivity constant or mains frequency harmonic extraneous light sources remain undetected only if the detector itself is not moved Due to its short ...

Page 8: ...0 0 4 5 Wave length µm Spectral emission of radiation of luminous and nonluminous flames at 1 500 K extract from VDI Report no 423 1981 a Black body radiation b Pulverized coal flame c Oil flame d Gas flame 100 10 1 1 1 5 2 5 4 Wave length µm Typical relative sensitivity 2 3 3 5 7719d02e 0302 Flames Legend Sensitivity of flame detector ...

Page 9: ... X10 02 4 X10 02 2 LMV5 sw Measurement of the detector s signal with a Voltmeter is not normally required since the flame signal s intensity is shown on the AZL5 display and operating unit Drawing of disposition Mounting kit is supplied completely assembled Clamp Adapter sleeve Adapter nipple heat insulator 7719z01 0314 Heat insulation glass Measurement of the detector current AGG2 110 ...

Page 10: ...IR ca 10 ca 10 7719z04 0216 IR Infrared rays L Available cable length see Type summary 40 5 6 144 5 69 6 8 162 8 22 18 55 7 7719m08 0603 L IR c a 1 0 c a 1 0 7719z05 0216 IR Infrared rays L Available cable length see Type summary QRI2B for lateral illumination QRI2B viewing angle Legend QRI2A for frontal illumination QRI2A viewing angle Legend ...

Page 11: ...ont d Cable ends stripped Brown Blue 7 40 7719m01e 0302 Black 1 0 5 Mounting kit AGG2 110 34 70 7719m11 1013 25 3 4 14NPSM 12 24 SW24 6 5 Pg9 7 5 28 5 1 2 14NPSM 7719m06 0302 Connecting cable Clamp 4 199 8806 0 adapter sleeve heat insulating piece Adapter AGG2 120 ...

Page 12: ... 18 15 30 R4 3 10 24 48 Company logo to LN 3 8380 0102 0 2 mm elevated 7719m09e 0608 R40 36 24 3 R0 3 10 R2 7 R2 R4 18 24 48 3 3 15 30 2 5 Company logo to LN 3 8380 0102 0 2 mm elevated 7719m10e 0114 Mounting coupling AGG04 Flange straight 4 241 8898 0 Flange with radius 4 241 88550 ã2018 Siemens AG Building Technologies Berliner Ring 23 D 76437 Rastatt Subject to change ...

Reviews: