Siemens QMX3.P35H Series Quick Start Manual Download Page 2

    


Siemens 

 

A6V11521633_en--_b 

Smart Infrastructure 

 

2020-11-09 

 

  

Use / compatibility 

The room automation station determines the functions of both LCD display and touch 

screen. 
●  Measure and indicate the room temperature 
●  Display humidity, PM2.5, and CO

2

 

●  Operate room functions 
●  Indicate external information (outdoor temperature, outdoor humidity) 

  

Mechanical design 

 

●  The devices are designed for a common conduit box (A). 

–  Conduit box: Keep in mind the dimensions of the conduit box! 

●  The base plate (B) has screw holes for all common conduit boxes (A). 

The screw head height must not exceed 3 mm. 

●  The device (C) incorporates a KNX PL-Link plug, a tool plug, sensor element and LCD 

touch panel. 

The cable can be hidden into conduit box. 

●  A KNX plug is enclosed with the devices. 

  

Type summary 

 

Product no. 

Stock no. 

Color type 

Suitable for 

QMX3.P35H 

S55624-H137 

White, RAL9003 

Square conduit box 

1)

 

QMX3.P35H-BSC  S55624-H139 

Black, Pantone Black C 

Square conduit box 

1)

 

QMX3.P38H 

S55624-H138 

White, RAL9003 

Square conduit box 

1)

 

QMX3.P38H-BSC  S55624-H140 

Black, Pantone Black C 

Square conduit box 

1)

 

 

 

1) 

Conduit boxes are not included and must be ordered separately. 

  

Product documentation 

 

Title 

Document ID 

Mounting instruction 

A6V11521631 

Mounting and installation PXC3.., DXR2.. 

A6V10361918 

CE declaration 

A6V11579510 

RCM declaration 

A6V11579512 

Environmental product declaration 

A5W90009021 

 

 

Related documents such as environmental declarations, CE declarations, etc., can be 

downloaded at the following Internet address: 

http://siemens.com/bt/download

 

Summary of Contents for QMX3.P35H Series

Page 1: ...with KNX PL Link for Desigo Room Automation Functions depending on type 160 x 128 pixel touch screen Energy efficiency function Green Leaf Built in room temperature sensor LCD display for room temperature CO2 humidity PM2 5 operating mode etc User interface for lighting blinds and scene control QMX3 P38H KNX PL Link plug play Powered over KNX PL Link Sound buzzer White or black housing ...

Page 2: ...LCD touch panel The cable can be hidden into conduit box A KNX plug is enclosed with the devices Type summary Product no Stock no Color type Suitable for QMX3 P35H S55624 H137 White RAL9003 Square conduit box 1 QMX3 P35H BSC S55624 H139 Black Pantone Black C Square conduit box 1 QMX3 P38H S55624 H138 White RAL9003 Square conduit box 1 QMX3 P38H BSC S55624 H140 Black Pantone Black C Square conduit ...

Page 3: ...X PL Link plug Use the tear off label with the barcode on the packaging display and stick it on the floor plan to prepare commissioning for several room operator units per room automation station The same barcode label with unique identifier is available on the device Mounting and installation Mounting The devices are suitable for wall and flush mounting with conduit box Recommended height 1 50 m ...

Page 4: ...minal is for KNX PL Link Observe all local installation regulations CAUTION The devices are not protected against accidental connection to AC 230 V Operation Operational setting NOTICE Operation and display oft he room operator unit depend on the control program of the room automation station Main page displaying HVAC functions for all types QMX3 P35H QMX3 P38H ...

Page 5: ...ing Cooling Green leaf An arrow indicates that an element can be operated Display of the relative or absolute setpoint for temperature humidity Indicates that the room operator unit is locked by the system Fan speed Fan AUTO Fan OFF Fan 1 Fan 2 Fan 3 Navigation Toggle the display setpoint setting between temperature humidity CO2 PM2 5 The black bar points to the displayed information Occupancy sta...

Page 6: ...page displaying lighting blinds and scenes QMX3 P38H QMX3 P38H BSC Example Icon Description Control lights Light A Light B Light C Light D Control blinds Blind 1 Blind 2 Blind 3 Blind 4 Meeting Presentation Break Occupied Unoccupied Cleaning Do not disturb Amusement ...

Page 7: ... or ABT to the room automation station and activate the online commissioning function 2 Load web page KNX PL Link identification Activate the identification function The room automation station now waits for a signal from the room operator unit 3 On the room operator unit enter Engineering mode For unconfigured units press the blank space on the bottom right corner for at least 5 seconds For QMX3 ...

Page 8: ...ce is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty Technical data on specific applications are valid only together with Siemens products Siemens rejects any and all war...

Page 9: ...suring accuracy 25 C 0 5 K Display Type LCD touch screen Information displayed depends on the application in the room automation station Room temperature humidity CO2 PM2 5 Outdoor temperature humidity Setpoint adjustment Operating mode Auto or manually selected fan speed Occupancy Vacancy Scenes Ports interface Type of port between room automation station and operator unit KNX PL Link Baud rate 1...

Page 10: ...0721 3 1 Transport as per EN 60721 3 2 Operation as per EN 60721 3 3 Class 1M2 Class 2M2 Class 3M2 Standards directives and approvals EU conformity CE A6V11579510 RCM conformity A6V11579512 REACH Regulation EC No 1907 2006 Registration Evaluation Authorization and Restriction of Chemicals REACH Environmental compatibility The product environmental declaration A5W90009021 contains data on environme...

Page 11: ...iring and communications do not work on interchanged wires Do not connect the KNX KNX PL Link bus to the tool plug only the tool Connect the tool Connect ABT to load the application in the room automation station or for service purposes Directly to the room automation station To the room unit using the tool cable and the OCI702 service interface see data sheet A6V10438951 Tool plug 2 5 mm jack RJ4...

Page 12: ... Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11521633_en _b Edition 2020 11 09 Dimensions Dimensions in mm ...

Reviews: