Document No. 129-104
Installation Instructions
December 11, 2017

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. APOGEE is a registered trademark or Siemens Industry, Inc. Other product or company names mentioned herein
may be the trademarks of their respective owners. © 2017 Siemens Industry, Inc.

Siemens Industry, Inc.

Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000

Your feedback is important to us. If you have
comments about this document, please send them
to

[email protected]

Document No. 129-104

Printed in the USA

Page 4 of 4

CAUTION:

To prevent equipment damage, do the
following:

If the room unit is powered by AC:

 

AC Supply must be type NEC Class 2
and earth grounded at the secondary
neutral.

 

Room Unit ACN (GND) must be
connected to the controller common.

 

If the controller has a floating common,
that common must be connected to the
same earth ground point as the controller
AC supply.

If the room unit is powered by isolated
DC:

 

Where power is current limited up to 300
mA, it is not required to earth ground the
controller isolated common.

Room Unit DC-(GND) must be connected
to the controller common.

CAUTION:

Follow manufacturer’s Installation
Instructions and Wiring Guidelines for
connecting the controller to the Room
Unit.

For Siemens Controllers:

  APOGEE Controllers with common already

earth grounded are TXIO used on PXC
Modular, PXC Compact 36 Expansion and
P1 BIM or PTM used on MBC and RBC.
These do not require the earth ground wire
to be connected to the controller.

APOGEE Controllers with floating common
are PXC Compact 16/24/36, MEC, PXM,
LON TEC and PPM. These require the
earth ground wire to be connected to the
controller.

Figure 6.  Typical Wiring Base.

(All terminals may not be present.)

Pin No.

Function

Units with Blank Front

 

1

DC+ or ACH

 

2

DC- or ACN (GND)

 

3

Temp Output

 

4

Humidity Output

 5*

Passive Temp

 6*

Passive Temp Common

Units with Display

 

1

DC+ or ACH

 

2

DC- or ACN (GND)

 

3

Temp Output

 

4

Humidity Output

 5*

Passive Temp

 6*

Passive Temp Common

 

7

Setpoint Output

 

8

Override

 

9

Override Common

* Not available on “SS” models.

NOTE:

If active temperature (0 to 5V/0 to 10V/4 to
20 mA) (Pin 3) rather than passive/resistive
temperature is used, Passive Temp Common
(Pin 6) does not need to be terminated.

The installation is now complete.

Summary of Contents for QFA3212.FWxN

Page 1: ...ccessories AQA2200 INTL Room Unit Back Plate 10 pack 563 102 GSKT KIT Room Sensor Insulating Gasket 10 pack For hollow wall installations Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Item Number 129 104 Rev JA Expected Installation Time 20 minutes Required Tools Sizes 1 and 2 Phillips screwdrivers Small and medium flat blade scr...

Page 2: ...ce 3 Cut a 1 inch 25 mm center hole with a hole saw NOTE It is recommended that you use the optional Insulating Gasket on the back of the Unit Base for hollow wall installations When applying the adhesive backed gasket to the back of the unit base orient the gasket so that the cut out arrow portion of the gasket is in the upper lefthand quadrant of the unit base The sensor base has an UP arrow mol...

Page 3: ...5 Changing Display to C 3 Snap the room unit cover to the room unit base plate by first hooking the room unit front to the top latches and then rotating the cover downward until it latches 4 Loosen the safety set screw at the bottom of the base one or two revolutions to lock the cover to the base Be careful not to loosen too far as the screw can be completely removed from the base Electrical Box a...

Page 4: ...red by isolated DC Where power is current limited up to 300 mA it is not required to earth ground the controller isolated common Room Unit DC GND must be connected to the controller common CAUTION Follow manufacturer s Installation Instructions and Wiring Guidelines for connecting the controller to the Room Unit For Siemens Controllers APOGEE Controllers with common already earth grounded are TXIO...