6/8 

Siemens 

QAX34.1 – Room unit with PPS2 interface 

CA2N1645en_02 

Building Technologies 

 

30 Jun 2009 

Technical data  

 

Supply voltage 

Operating voltage range 

SELV / PELV DC 12 ... 15 V 

 

The room unit receives its power from the connected controller, via the PPS2 interface 

 

Power consumption (from controller) 

Max. 0.10 VA 

Function data 

Temperature sensor 

 

 

Measuring element 

NTC resistor 

 

Measuring range 

0 ... 40 °C 

 Response 

time 

 8 min 

 

Accuracy (5 ... 30 °C) 

 0.5 K 

 Accuracy 

(25 

°C) 

 0.25 K 

 Setpoint 

correction 

 

 

Correction range (determined by controller) max. 

 10 K (default 

 3 K) 

 

Accuracy over full correction range 

10 % 

Display Type 

LCD 

 

Functions displayed 

– Room temperature 
– Setpoint adjustment 
– Control mode 
– Manually selected fan-speed 
– Control sequence 
– Error code 

Interfaces 

Type of interface between controller and  
room unit  

PPS2  
(point-to-point interface, Version 2) 

 

Baud rate 

4.8 kbit/s 

Cable connections 

Connection terminals (screw terminals) 

Stranded or solid conductors   
0.8 ... 2.5 mm

2

 

 

Single cable length controller – Room unit 

See Installation guidelines: 
DESIGO RXC: CA110334,  
DESIGO RXB & RXL: CM110381 
DESIGO RXA: CA2Z3884 
DESIGO PX:    CA110396 

 

Cable type 

2-core or 4-core, twisted pairs,  
unscreened  

 

Connecting cable for service tool 

Off-the-shelf, max. 3 m 

Housing protection standard  Protection standard to EN 60529 

IP 30 

Protection class 

Insulation protection class 

III 

Ambient conditions 

IEC 721 

Operation 

Transport 

 

Ambient air conditions 

Class 3K5 

Class 2K3 

 

Temperature 

0 ... 50 °C 

– 25 ... 70 °C 

 

Humidity 

< 85 %rH 

< 95 %rH 

 

Mechanical conditions 

Class 3M2 

Class 2M2 

Standards and directives 

Product standard Automatic electronic controls 

for household and similar use 

 
EN 60730-1 

 Electromagnetic 

compatibility 

 

 

Immunity (industrial & domestic) 

EN 60730-1 

 

Emissions (domestic) 

EN 60730-1 

 

 compliance 

 

 

Meets requirements of EMC directive 

2004/108/EC 

 

UL

 compliance 

UL916 

 

 C-Tick conformity (EMC) 

AS/NZS 61000-6-3 

Environmental

 

compatibility  The product environmental declaration 

CA2E1645 contains data on RoHS compli-
ance, materials composition, packaging, envi-
ronmental benefit, disposal 

ISO 14001 (Environment) 
ISO 9001 (Quality) 
2002/95/EC (RoHS) 

Dimensions See 

“Dimensions” 

 

Color Housing 

front 

NCS 

0502-G, 

 RAL 9003 signal white

 

Housing, base unit, rocker switches 

RAL 7035 light grey 

Weight Excluding 

packaging 

0.12 

kg 

Summary of Contents for QAX34.1

Page 1: ...it is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of the room controller The functions of the LCD display are determined by the controller If manual fan speed control is enabled the room unit is suitable for control of a fan coil system It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorp...

Page 2: ...etpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80083 80084 Socket for the commissioning and service tool or service terminal 80166A Room temperature display and sequence heating or cooling Rocker switch for room temper...

Page 3: ...ress the switch once to switch from a display of the current room temperature to a display of the setpoint Each further operation of the or switch raises or lowers the setpoint by 0 5 K or 1 0 F the unit of measurement is determined by the controller The controller also determines the maximum adjustment range allowed In normal operation the following may be displayed depending on the controller co...

Page 4: ...oom units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller DESIGO RX uses four core cables DESIGO PX uses two core cables see the respec tive installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recess...

Page 5: ...ce tool initiates a wink command the type of controller connected will be displayed on the room unit For example Controller type Display RXC21 1 RXC30 1 Operating notes During operation and commissioning the LCD display also indicates errors as follows Display Description Error type C No communication with controller for more than 64 s 02 Firmware version e g Version 2 0 D Room temperature sensor ...

Page 6: ...IGO RXC CA110334 DESIGO RXB RXL CM110381 DESIGO RXA CA2Z3884 DESIGO PX CA110396 Cable type 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temper...

Page 7: ...voltage CP 1 Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus DESIGO RXC CLA C 4 With LONWORKS bus DESIGO RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus DESIGO RXC CLA With LONWORKS bus DESIGO RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Ex...

Page 8: ...ns QAX34 1 Room unit with PPS2 interface CA2N1645en_02 Building Technologies 30 Jun 2009 Dimensions 9 5 32 34 4 2 60 80088 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Reviews: