Principle of 
Operation 

The sensor's nickel sensing element measures the air or medium temperature. 
The resistance of the sensing element changes as a function of the ambient 
temperature. 

Mechanical Design 

The QAP22 Cable Temperature Sensor sensing element is incorporated in the 
1000 Ohm Nickel RTD sensors. It is a nickel resistor housed in a metal sleeve so that it 
is mechanically and electrically protected. The connecting cable inside the metal sleeve 
is provided with a strain relief. 

 

The QAA24U and QAA25U room sensors have a temperature sensor mounted 
on a circuit board. 

 

The plastic housing has a detachable wall plate. 

Specifications 

QAM2020.045, 
QAM2020.020, 
QAM2020.010, 
QAE2020.005, 
QAC2020U and QAP22 

Range of use 

–13°F to 203°F (

25°C to 95°C) 

Sensing element 

Siemens Ni1000 at 32°F (0°C) 

Permissible ambient temperature 
 

Cable 

–13°F to 203°F (

25°C to 95°C) 

 

Intermittent (two hours/day) 

–13°F to 230°F (

25°C to 110°C) 

Permissible ambient humidity 

95% rh 30 days 

 

Connecting cable (QAP22) 

PVC, 20 AWG 

 

Length 

6 feet (1.8 m) 

QAA24U and QAA25U 

Range of use 

32°F to 122°F (0°C to 50°C) 

Sensing element 

Siemens Ni1000 at 32°F (0°C) 

Permissible ambient temperature 

32°F to 122°F (0°C to 50°C) 

Permissible ambient humidity 

<85% rh 

Wiring screw terminals for wires of 

2 × 16 AWG or 1 × 12 AWG 

 

 

 

Minimum 20 AWG 

Installation 

Complete installation instructions are provided with the sensors. 

Accessories 

AQM2000  Flange gasket kit (if adjustable depth is required for QAM2020.045 duct 

point temperature sensors) 

ARG70 

Wall plate kit (required for wall box mounting) 

Wiring 

 
 
Legend: 
 

B1  Temperature sensor 

signal 

B2  Setpoint signal 
M  Measuring, neutral 

 

 

 

 

 

 

Figure 1.  QAP22,  

QAM2020.045, QAM2020.020, 

QAM2020.010 and 

QAE2020.005. 

Figure 2.  QAA24U. 

Figure 3.  QAA25U. 

 