Safety, approvals, EMC
7.3 Approvals
SITOP PSU300M/300B
Manual, 11.2014, C98130-A7574-A2-2-7629
61
7.3
Approvals
6EP1436-3BA10 (24 V/20 A)
6EP1456-3BA00 (48 V/10 A)
CE marking
Yes, (2004/108/EG and 2006/95/EG)
Yes, (2004/108/EG and 2006/95/EG)
UL/cUL (CSA) approval
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection
EPS 12 ATEX 1 442 X
IECEx EPS 14.0062X
II 3G Ex nA nC IIC T4 Gc
cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01-2007)
CB approval
Yes
Yes
SEMI F47 compliance
Fulfilled
-
Marine approvals
GL, ABS
GL, ABS
6EP1424-3BA00
(12 V / 20 A)
6EP1436-3BA20
(24 V / 17 A)
6EP1437-3BA20
(24 V / 30 A)
CE marking
Yes, (2004/108/EG and
2006/95/EG)
Yes, (2004/108/EG and
2006/95/EG)
Yes, (2004/108/EG and
2006/95/EG)
UL/cUL (CSA) approval
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
cULus-Listed (UL 508,
CSA C22.2 No. 107.1),
File E197259
Marine approvals
-
GL
-
7.4
EMC
6EP1436-3BA10 (24 V / 20 A)
6EP1456-3BA00 (48 V / 10 A)
6EP1424-3BA00 (12 V / 20 A)
6EP1436-3BA20 (24 V / 17 A)
6EP1437-3BA20 (24 V / 30 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
80 … 1000 MHz 25 V/m 1000 … 2700 MHz 10 V/m
High-speed transient dis-
turbances (burst)
EN 61000-4-4
4 kV at line supply connections, 2 kV at the DC output
Surge voltages
EN 61000-4-5
3 kV symmetrical at the line connections
6 kV unsymmetrical at the line connections
500 V symmetrical/unsymmetrical at DC output cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 … 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Emitted interference
EN 55022
Class B