QUICK REFERENCE GUIDE 

INSTALL PSO 4000 CROSSING 

ASSEMBLY MODULES

 

Document Number SIG-QG-10-06 

Version A.1 

The following procedure should be used when installing 
Phase Shift Overlay 4000 (PSO 4000) Track Circuits utilizing 
PSO 4000 Transmitter, 7A471 and PSO Crossing Assembly, 
7A474. 

WARNING 

VERIFY THAT THE PSO 4000 
TRANSMITTER’S AND CROSSING 
ASSEMBLY’S SOFTWARE,  FREQUENCY, 
AND ADDRESS FORMATS ARE AS 
SPECIFIED BY THE RAILROAD’S OR 
AGENCY’S APPROVED WIRING OR 
INSTALLATION DIAGRAM. FAILURE TO DO 
SO MAY LEAD TO INCORRECT OR UNSAFE 
OPERATION OF THE TRACK CIRCUIT. 
IF ANY RECEIVER IS CALIBRATED IN POOR 
BALLAST CONDITIONS, IT MUST BE RE-
CALIBRATED WHEN BALLAST CONDITIONS 
IMPROVE. 
FAILURE TO FOLLOW THE RAILROAD’S OR 
AGENCY’S APPROVED WIRING OR 
INSTALLATION GUIDELINES REGARDING 
RECEIVER SETTINGS AND CALIBRATION 
MAY LEAD TO POSSIBLE  UNSAFE 
OPERATION OF THE TRACK CIRCUIT. 
AFTER CALIBRATION, VERIFY THAT THE 
TRACK CIRCUIT DE-ENERGIZES WHEN THE 
TRACK CIRCUIT IS SHUNTED WITH THE 
APPROPRIATE  CALIBRATION  RESISTANCE 
(0.06, 0.2, 0.3, 0.4, OR 0.5 OHMS). FAILURE 
TO DO SO MAY LEAD TO  INCORRECT OR 
UNSAFE OPERATION OF THE TRACK 
CIRCUIT. 
FOLLOWING  INSTALLATION OR AFTER 
ANY  RECEIVER MENU  CHANGES HAVE 
BEEN MADE, RECALIBRATE THE RECEIVER 
AND TEST FOR PROPER OPERATION  PER 
THE REQUIREMENTS SPECIFIED IN TABLE 
7-2 AND TABLE 7-3 OF SIG-00-07-06, PSO 
4000 I & I MANUAL. 

Perform the following steps to install the PSO 4000 units: 

1.

 

Install and connect all PSO equipment in the Wayside 
Signaling Station (WSS) per the railroad’s or agency’s 
approved wiring or installation diagram. 

2.

 

Connect all required wiring per the railroad’s or 
agency’s approved wiring or installation diagram. 

3.

 

Prior to beginning programming, verify LED 
functionality using the *CHECK LED portion of the 
TEST menu per Section 5.2.7.2. If any LED fails to light 
following test, replace the unit. 

4.

 

Program each unit by performing Set to Default. Then 
proceed through the setup (SETP) menu to program 
each unit per the railroad’s or agency’s approved 
written instructions. 

With each unit properly installed and programmed per 
written instructions, calibrate the approaches (RX1 or RX2) 
as follows: 

1.

 

When the track ballast is good, connect a test shunt 
(hardwire, 0.06-ohm, 0.2-ohm, or as required) across 
the track at the receiver track connections of the 
approach. When the ballast is poor, connect the shunt 
across the track at a point 30 feet beyond the 
receiver track connections of the approach. Verify 
solid connections of the shunt to each rail.  
Scroll down the Main Menu until CAL appears on the 
display. Then: 

 

Press the MENU Button for two (2) seconds until 
RX1 (RX2) CAL appears. 

 

Hold the MENU Button down until the release 
(REL) message appears. Release the MENU Button 
immediately once the release (REL) message 
appears. 

 

As soon as the MENU button is released, the 
armed (ARMD) message appears. Immediately 
press and release the MENU Button as soon as 
the ARMD message appears. This starts the 
calibration process. If the MENU Button is not 
pressed within two (2) seconds, the calibration 
process cancels and the calibration process must 
be restarted.  

 

*RX1 (*RX2) CAL flashes during the calibration 
process.  

 

PASS or FAIL appears for two (2) seconds when 
calibration is complete. When PASS appears, 
continue to Step 3. If FAIL appears, the 
CALIBRATION REQUIRED LED remains lit. 

 

 

 

Diagnostic

Menu

Navigate

+

N

B

Port

Power

Health

OUT

IN1

IN2

TX Enable

+

+

+

Made in USA

07-06_7A474_APP_DWG

07-08-09

PSO 4000 TRANSMITTER, 7A471

PSO 4000 CROSSING

ASSEMBLY, 7A474

SOLID STATE CROSSING

CONTROLLER IV (SSCC IV) , 91215

WOT (RX1)

TUNED RECEIVER

COUPLER, 7A355-f

EOT (RX2)

TUNED RECEIVER

COUPLER, 7A355-f

PSO 4000 TRANSMITTER, 7A471

Diagnostic

Menu

Navigate

Island

RX2

RX1

Island

RX2

RX1

+

N

B

Port

Power

Health

XR

Stick

OUT2 

OUT1

OUT3

IN1

IN2

Island LOS

+

+

+

+

+

+

+

Made in USA

Diagnostic

Menu

Navigate

+

N

B

Port

Power

Health

OUT

IN1

IN2

TX Enable

+

+

+

Made in USA

=   TWIST TWO TURNS PER FOOT

=    022700-1X EQUALIZER, H.D.

=    022585-1X ARRESTER, H.D.

=    EARTH GROUND

LEGEND

PSO 4000 TRACK WIRES MAY BE

#9 A.W.G. FOR LENGTHS UP TO

100 FEET. FOR LENGTHS BETWEEN

100 AND 300 FEET, TRACK WIRES

SHOULD BE #6 A.W.G. IF LENGTHS

EXCEED 300 FEET, REFER TO

SECTION 7.2.3 FOR TRACK WIRE

SELECTION AND SECTION 3.3 FOR

COUPLER USAGE AND

INSTALLATION.

PSO 4000 UNIT INPUTS AND

OUTPUTS ARE CONNECTED PER

THE RAILROAD'S OR AGENCY'S

WRITTEN INSTRUCTIONS.

WOT, EOT, AND OXT MUST EACH

BE SET TO SEPARATE PSO AND

ISLAND FREQUENCIES.

SET OUT1= XR TO UTILIZE THE

SSCC.

SSCC UNIT MAY BE SSCC III, SSCC

III (PLUS) OR SSCC IV. THE SSCC

IS WIRED PER THE RAILROAD'S

OR AGENCY'S APPROVED WIRING

DIAGRAM.

NOTES

1.

2.

3.

4.

5.

MIN.#9 AWG TWISTED PAIR

MIN.#9 AWG TWISTED PAIR

+

-2- 

Copyright 

©

 2010-2014 Siemens 

All Rights Reserved 

-8- 

-7- 