Siemens POWERS 134-1861 Technical Instructions Download Page 4

Technical Instructions  

POWERS Controls 134-1861 Humidistat 

Document Number A6V11435226 
May 9, 2019 

Page 4 

Siemens Industry, Inc.

 

 

Installation

 

 

CAUTION: 

Do not remove the humidistat cover during installation. The sensing 
element must be carefully protected against accidental damage. All wiring 
and mounting can be completed without removing the cover. 

 

 

WARNING: 

Shock hazard. 

Disconnect the power supply before wiring connections are 

made to prevent electrical shock or possible damage to the equipment. 

 

1.  Select the proper mounting location (see 

General Guidelines

) and install a 

vertical or horizontal wall box 4 to 5 feet (1.2 to 1.5 m) above the floor. 

2.  Run conduit or cable, as required by national and/or local electric codes, from 

the wall box to the equipment to be controlled. Leave approximately 6 inches 
(152 mm) of wire for connection to the humidistat terminals. 

3.  Remove the humidistat mounting plate by loosening the mounting plate locking 

screw (see Figure 1) and lifting and removing the plate from the base. 

4.  Pull wires through the mounting plate and fasten the plate, grounding screw end 

up, to the wall box with the screws provided. 

5.  Strip the wires and connect to the proper terminals on the back of the humidistat. 

See 

Wiring Diagrams

NOTE:

 Use the terminal screws provided (8-32 × 1/4 in. binder head). 

Substitution of other screws may cause problems in making proper connections. 

6.  Connect the grounding provision of the humidistat to the branch circuit ground. 

7.  Hook the two slots in the humidistat base over the projections on the mounting 

plate and swing the humidistat into place. Push the wires back flush into the wall 
box. 

8.  Securely tighten the mounting plate locking screw. 

The installation is now complete. 

 

 

 

Figure 1.  134-1861 Humidistat. 

 

Summary of Contents for POWERS 134-1861

Page 1: ...ion and dehumidification The differential of the 134 1861 is fixed at approximately 6 RH Features Human Hair Sensing Element Provides stable accurate measurement 1 4 HP 6A Rated Contacts Permit direct operation of many fans in commercial applications High low Adjustable Knob Range Stops Allow adjustments within a desired range Enclosed Pennswitch Provides dust protection for contacts Mounting Plat...

Page 2: ...or systems alarm supervisory systems that protect against or warn of control failure Operation The humidistat has a setpoint range of 0 to 70 RH as well as humidification off HUM OFF and dehumidification off DEH OFF positions At the HUM OFF position the C to L terminal circuit is open and the C to H terminal circuit is closed At the DEH OFF position the C to H terminal circuit is open and the C to...

Page 3: ...ed Cover Brown markings on goldanodized aluminum Mounting Vertical or horizontal 2 4 in 51 102 mm wall box Wiring terminals Large 8 32 1 4 in binder head screws Weight 0 9 lb 0 4 kg Dimensions 4 71 2 96 2 94 in 120 75 75 mm Agency listings UL Guide No XAPX File E6688 CSA Class No 4813 02 File LR948 Mounting and Installation General Guidelines Locate the 134 1861 as follows on an inside wall away f...

Page 4: ...ed Leave approximately 6 inches 152 mm of wire for connection to the humidistat terminals 3 Remove the humidistat mounting plate by loosening the mounting plate locking screw see Figure 1 and lifting and removing the plate from the base 4 Pull wires through the mounting plate and fasten the plate grounding screw end up to the wall box with the screws provided 5 Strip the wires and connect to the p...

Page 5: ...Position the horizontal faceplate over the factory installed vertical faceplate Ensure that the plate is positioned straight and even to over the existing plate 5 Firmly press the horizontal faceplate onto the humidistat cover 6 Replace the adjustment knob The installation is now complete Wiring Diagrams Figure 2 Typical Wiring Diagram of a 134 1861 Used to Reduce Excessive Humidity in a Well Cons...

Page 6: ...e following procedures to set the high and low range stops High Range Stop 1 Set the adjustment knob to the maximum desired RH setting 2 Pull the adjustment knob off the humidistat cover 3 Loosen the bottom cover screw and remove the humidistat cover CAUTION Equipment damage hazard Avoid contact with the human hair sensing element Contact with the hair element can affect control accuracy and or pr...

Page 7: ...see Figure 7 and rotate it clockwise until it is against the stop pin C 5 Release the tab making sure it fits into the nearest notch 6 Replace the humidistat cover tighten the bottom cover screw and replace the adjustment knob 7 Rotate adjustment knob to desired normal operating setpoint Figure 7 134 1861 Humidistat Range Tabs and Stop Dial Lock The high and low range stops can be set to keep the ...

Page 8: ... 8 Dial Lock Continued 4 While holding the dial firmly in place keep the setting in line with the calibrating mark press Tab A and rotate it counterclockwise until it is against Stop Pin C Press Tab B and rotate it clockwise until it is against Stop Pin C See Figure 7 5 Ensure each tab fits into the notch closest to the stop 6 Replace the humidistat cover tighten the bottom cover screw and replace...

Reviews: