background image

Technical Instructions  
Document No. 155-199P25 
October 24, 2005 
 

Page 2

  

Siemens Industry, Inc. 

 

Ordering a Valve 
Plus Actuator 
Assembly 

To order a complete valve plus actuator assembly from the factory, combine the 
actuator prefix code with the suffix of the valve assembly product number. See 

Technical Bulletin (TB) 252

 (155-307P25) for selection procedure and ordering codes. 

Valve assemblies can be ordered using the numbers in Table 1.  

Specifications 

Line size 

1/2 to 1 inch (15 to 25 mm) 

Capacity 

See Tables 3 and 4 and Figure 1 

Body style 

Globe 

Seat style 

Metal-to-metal 

Action    

Three-way mixing 

Valve body rating  

ANSI Class 250; See Table 2 

Stem travel (Stroke) 

7/32-inch (5.5 mm) 

Material 

Body 

 

UNS CA844 bronze  

 

 

 

or forged brass C37700  

Body trim 

Brass 

Stem 

 

Stainless steel ASTM A582 Type 303 

Packing  

Ethylene propylene O-ring 

Operating 

Controlled medium  

Water, glycol solutions to 50% 

Medium temperature range 

35°F to 250°F (2°C to 120°C) 

Maximum inlet pressure  

See Table 2 

Maximum recommended differential pressure 
for modulating service 

25 psi (173 kPa) 

Rangeability  

 

Cv <1 

>50:1 

 

Cv >1 

>100:1 

Close-off pressures 

See Table 5 and Figure 2 

Close-off ratings  

According to ANSI/FCI 70-2 

Leakage rate 

Class IV (0.01% of Cv) 

Flow characteristics  

Linear 

Miscellaneous 

Canadian Registration Numbers 

0H7645.5 

 

 

 

0C0838.9 

Mounting location  

NEMA 1 (interior only) 

Dimensions 

See Tables 6 and 7 and  

 

 

 

Figures 4 and 5 

Valve Weight 

See Table 6 

Service Kit 

Protective black knob 
to cover the bonnet 
and threads 

 

4 268 8895 0 

 

 

Summary of Contents for Powermite 599 Series

Page 1: ...0 01 of Cv Application A typical application for the Powermite three way valve is the mixing of hot or chilled water for convectors fan coil units unit conditioners radiation reheat coils and similar terminal units requiring an actuator that delivers a minimum of 45 pounds force 200 N Product Numbers Table 1 Product Numbers Flow Rate Line Size Product Cv Kvs inch mm Number 0 4 0 34 1 2 15 599 0113...

Page 2: ...travel Stroke 7 32 inch 5 5 mm Material Body UNS CA844 bronze or forged brass C37700 Body trim Brass Stem Stainless steel ASTM A582 Type 303 Packing Ethylene propylene O ring Operating Controlled medium Water glycol solutions to 50 Medium temperature range 35 F to 250 F 2 C to 120 C Maximum inlet pressure See Table 2 Maximum recommended differential pressure for modulating service 25 psi 173 kPa R...

Page 3: ...0 8 8 10 1 11 3 12 4 13 9 2 5 3 5 4 3 5 0 5 6 6 1 7 1 7 9 9 7 11 2 12 5 13 7 15 8 17 7 19 4 22 4 5 7 7 8 0 8 9 10 11 3 12 6 15 5 17 9 20 0 21 9 25 28 31 35 3 4 6 3 8 9 10 9 12 6 14 1 15 4 17 8 20 24 28 32 35 40 45 49 55 1 10 14 1 17 3 20 22 24 28 32 39 45 50 55 63 71 77 87 Table 4 Maximum Water Capacity Cubic Meters per Hour m3 hr Valve Size in mm Pressure Differential kPa 1 10 20 30 40 50 60 80 K...

Page 4: ...esired pressure drop 5 psi Choose a 1 inch 25 mm valve Cv 10 Table 5 Close off Pressures Action Valve Size Inches mm SSB Actuator psi kPa NC Upper port 1 2 0 4 Cv 1 6 15 mm 0 34 Kvs 1 37 70 483 1 2 2 5 Cv 4 15 mm 2 15 Kvs 3 44 40 276 3 4 and 1 20 mm and 25 mm 30 207 NO Bottom port 1 2 0 4 Cv 1 6 15 mm 0 34 Kvs 1 37 25 172 1 2 2 5 Cv 4 15 mm 2 15 Kvs 3 44 15 103 3 4 and 1 20 mm and 25 mm 10 69 ...

Page 5: ... hold the last commanded position See the Technical Instructions of the various actuators for additional information Figure 3 Sizing The sizing of a valve is important for correct system operation An undersized valve will not have sufficient capacity at maximum load An oversized valve can initiate cycling and the seat and throttling plug can be damaged because of the restricted opening Correct siz...

Page 6: ...tall the valve assembly so that the actuator is below horizontal or up side down Allow sufficient space for servicing the valve and actuator See Table 6 for valve body dimensions See Figure 5 and Table 7 for dimensions of the service envelope recommended around the actuator NOTE Instructions for field mounting an actuator wiring diagrams and start up are covered in the Technical Instructions and I...

Page 7: ...the Actuator and Recommended Service Envelope Dimensions in Inches Millimeters Actuator Actuator Prefix Code Valve line Size Center line to Top of Actuator H1 Service Height H Actual width of the Actuator W1 Service Width W SSB 254 255 1 2 15 4 7 8 124 13 1 8 330 3 1 4 83 11 1 4 282 3 4 20 4 7 8 124 13 1 8 330 3 1 4 83 11 1 4 282 1 25 5 1 8 130 13 3 8 335 3 1 4 83 11 1 4 282 ...

Page 8: ... Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 155 199P25 Printed in the USA Page 8 Parts Of The Valve Table 8 Three way Bronze Forged Brass Valves Item Part Name Part No Q ty Material 1 Bonnet Ass y 1 2 Spri...

Reviews: