![Siemens POS INPUT Reference Manual Download Page 17](http://html.mh-extra.com/html/siemens/pos-input/pos-input_reference-manual_377285017.webp)
17
Product Information on the Reference Manual Programmable Logic Controllers S7-300 Module Data Release 3
A5E00409892-01
1.1.7
Technical Specifications of the 338; POS-INPUT
Dimensions and Weight
Dimensions B x H x T
(mm)
40 x 125 x 120
Weight
Approx. 235 g
Voltages, Currents, Potentials
Rated load voltage L+
•
Range
•
Reverse polarity
protection
24 VDC
20.4 ... 28.8 V
No
Isolation
no, only against shield
Permitted potential
difference
•
between input
(M connection) and
central grounding point
of the CPU
1 VDC
Encoder supply
•
Output voltage
•
Output current
L+ –0.8 V
max. 900 mA, short
circuit–proof
Current dissipation
•
From the backplane
bus
•
From the load voltage
L+ (no load)
max. 160 mA
max. 10 mA
Power dissipation of the
module
typ. 3 W
Encoder inputs POS INPUT 0 to 2
Position decoding
absolute
Difference signals for SSI
data and SSI clock
according to RS422
Data transfer rate and cable
length of absolute value
encoders (twisted pair and
shielded)
•
125 kHz max. 320 m
•
250 kHz max. 160 m
•
500 kHz max. 60 m
•
1 MHz max. 20 m
Message duration of the
SSI transmission
•
125 kHz
•
250 kHz
•
500 kHz
•
1 MHz
13 bits 21 bits 25 bits
112
m
s 176
m
s 208
m
s
56
m
s 88
m
s 104
m
s
28
m
s 44
m
s 52
m
s
14
m
s 22
m
s 26
m
s
Monoflop time
2
16
m
s, 32
m
s, 48
m
s, 64
m
s
Digital inputs DI 0, DI 1
Isolation
no, only against shield
Input voltage
0-Signal: –3 V ... 5 V
1-Signal: 11 V ... 30.2 V
Input current
0-Signal:
v
2 mA
(quiescent current)
1-Signal: 9 mA (typ.)
Input delay
0 > 1: max. 300
m
s
1 > 0: max. 300
m
s
Maximum repeat frequency
1 kHz
Connection of a two–wire
BEROS, type 2
Possible
Shielded line length
600 m
Unshielded line length
32 m
Status, Interrupts, Diagnostics
Interrupts
•
Diagnostic interrupt
Parameters can be
assigned
Status display of digital
inputs
Group error/fault
LED (green)
LED (red)
Inaccuracy of the encoder value
Free running encoder value acquisition
(Standard Mode)
•
Maximum age
1)
(2
×
Message duration)
+ monoflop time
+ 580
m
s
•
Minimum age
1)
Message duration
+ 130
m
s
•
Jitter
Message duration
+ monoflop time
+ 450
m
s
Update rate
Evaluation of the message
every 450
m
s
Free–wheeling sensor value detection (Fast Mode)
•
Maximum age
1)
(2
×
Message duration)
+ monoflop time
+ 400
m
s
•
Minimum age
1)
Message duration
+
100
m
s
•
Jitter
Message duration
+
monoflop time
+ 360
m
s
Update rate
Evaluation of the message
every 360
m
s
Synchronous encoder value acquisition
•
Age
Encoder value at time T
i
of
the current PROFIBUS DP
cycle