Basic Steps for Connecting Devices to the 
DIN Rail 

The island bus establishes its own connection when 
TX-I/O devices are plugged into one another on a DIN 
rail. 

1. 

Slide out the mounting tabs. 

2. 

Align the channel on the back of the device with 
the DIN rail. 

3. 

Using a flat blade screwdriver, push in each 
mounting tab until it clips onto the DIN rail. 

4. 

Align an I/O module with the Power Supply or Bus 
Connection Module and slide the I/O module 
down over the TX-I/O island bus connector. 

5. 

Push in each mounting tab until it clips onto the 
DIN rail. 

 

Connecting Devices to the TX-I/O Island Bus. 

Completing the Installation 

 

CAUTION: 

 

For RS-485 ALN or FLN, terminate only one 
end of the shield wire on the enclosure earth 
ground. 

For a 3-wire system, 

 terminal is connected 

to reference wire. Protective ground terminal 
may be connected to earth ground. 

For a 2-wire system, 

 terminal is not 

connected. Protective ground terminal must 
be connected to earth ground. 

NOTE: 

Do not connect the power or network 
communication cable until instructed to do so 
during start-up. 

1. 

Terminate power wiring to the 24 Vac removable 
plug.  

2. 

If necessary, terminate wires to the 
communications terminals (CS and CD). 

The installation is now complete.

 

Summary of Contents for P1 BIM

Page 1: ... as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Required Tools and Materials Wire stripper side cutter Small flat blade screwdriver Digital multimeter DMM Expected Installation Time 7 minutes Prerequisites CAUTION No power wiring is connected to the field panel controller or other TX I O components at this time CAUTION The TX I O islan...

Page 2: ...us System Neutral must be connected to building approved earth ground at a single point only at the 24 Vac transformer Installation CAUTION Turn OFF AC power at the ON OFF switch in the Service Box or transformer enclosure CAUTION UL Listings require that NEC Class I and Class II wiring be kept separate from each other Use separate conduit and cable tie bars to separate Class I Digital Output DO w...

Page 3: ...X I O island bus connector 5 Push in each mounting tab until it clips onto the DIN rail Connecting Devices to the TX I O Island Bus Completing the Installation CAUTION For RS 485 ALN or FLN terminate only one end of the shield wire on the enclosure earth ground For a 3 wire system terminal is connected to reference wire Protective ground terminal may be connected to earth ground For a 2 wire syste...

Page 4: ...ed in the USA Page 4 of 4 Configuring the 4 Module P1 BIM 1 Power up the P1 BIM 2 Plug in the USB on both ends the device side to the P1 BIM the host side to the computer The device will be automatically recognized and installed 3 Open Windows Explorer 4 Find the USB device drive will say SIEMENS P1BIM Configuration Tool in the drives list 5 Open the drive 6 Double click P1BIMCFG exe to launch the...

Reviews: