Commissioning and parameterization 

The following parameters are checked or set during engineering and commissioning in the 
ETS engineering tool. 

Parameter 

Range 

Description 

Factory settings 

Tab card “standard” 

Adaptive positioning  On / Off 

Adaption of actual (if mechanically limited) 
opening range to position feedback 0...100% 

Off = No adaption / On = Adaption active 

Off 

Backup timeout 

0..60 min 

0 min = disabled 

Time interval to detect communication 
interruption. 

If disabled, the actuator drives to the last received 
setpoint until a new valid setpoint is received. 

30 min. 

Backup mode 

Backup position  
Keep last position 

Actuator behavior when the communication 
timeout has been exceeded (no setpoint received 
within the defined time interval). 

  Backup position: Actuator drives to defined 

position 

  Keep last position: Actuator keeps position 

without flow control 

Backup position 

Backup position  

0…100% 

Position the damper drives to in case of 
communication interruption 

50% 

Tab card “advanced” 

Hysteresis (COV) 
damper position 

1...20% 

Threshold for the damper position. COV below 
this value are not sent over the bus 

1% 

Min. repetition time 
damper position 

10...900 s 

Minimum waiting time until a COV above the 
hysteresis threshold is sent over the bus 

10 s 

Minimum damper 
position 

0...100% 

Electronic lower position limit 

0% 

Maximum damper 
position 

0…100% 

Electronic upper position limit 

100% 

Override position 1 

0...100% 

Damper position which can be triggered by the 
corresponding group object (with override priority) 

0% 

Override position 2 

0…100% 

Damper position which can be triggered by the 
corresponding group object (with override priority) 

100% 

 

 

Summary of Contents for OpenAir GDB111.1E/KN

Page 1: ... OpenAir Communicative Damper Actuators KNX PL Link G B111 1E KN Damper actuators 5 10 Nm with KNX communication GDB111 1E KN with 5 Nm nominal torque GLB111 1E KN with 10 Nm nominal torque Operating voltage AC 24 V Supports KNX S Mode LTE Mode and PL Link s ...

Page 2: ...ol www knx org ABT 4 0 2 Software Desigo Engineering Commissioning Tool A6V11159913 2 Release planned for April 2020 Product and software versions Product revision Series A Production period From 02 2020 Bus module FW version 4 25 ETS device profile v1d0 knxprod The ETS device profile can be downloaded at the following Internet address http siemens com hvac td Product documentation Title Topic Doc...

Page 3: ... rotation bracket Mounting positions IP54 protection in following mounting positions Accessory mounting holes 2 Cf mounting instr M4634 2 Not to be used for fixation of the actuator use anti rotation bracket instead Maintenance The damper actuators are maintenance free Disconnect the electrical connections from the terminals if you want to work at the device Disposal The device is considered elect...

Page 4: ...flashing a Factory reset in progress b When a connection test was triggered wait 4 Red steady a Device is in programming addressing mode b When a connection test was triggered Connection test failed 4 4 Function or part of the function available in PL Link operation only Addressing and bus test with push button The damper actuators can be set into addressing programming mode by push button Press p...

Page 5: ...d no setpoint received within the defined time interval Backup position Actuator drives to defined position Keep last position Actuator keeps position without flow control Backup position Backup position 0 100 Position the damper drives to in case of communication interruption 50 Tab card advanced Hysteresis COV damper position 1 20 Threshold for the damper position COV below this value are not se...

Page 6: ...arm 1 Alarm 3 Fault transmission Receive 1 0 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 4 Setpoint Receive 1 1 1 0 1 5 001 _Scaling 1 Byte 0 100 5 Damper position Transmit 1 1 0 1 0 5 001 _ Scaling 1 Byte 0 100 9 Overridden Transmit 1 1 0 1 0 1 002 _Bool 1 bit 0 False 1 True 10 Override position 1 Receive 1 1 1 0 1 1 003 _Enable 1 bit 0 Disable 1 Enable 11 Override position 2 Receive 1 1 1 0 1 1...

Page 7: ...sensitivity 2 Fault state Indicates whether the actuator is in fault state If yes read out group object 1 3 Fault transmission Enabling disabling the fault transmission Fault transmission is disabled by default no faults are transmitted from the actuator over the KNX bus 4 Setpoint Setpoint 0 100 for volume flow or position depending on the operating mode 5 Damper position Relative damper position...

Page 8: ...ion cables Cable length 0 9 m Power supply Number of cores and cross sectional area 2 x 0 75 mm2 Communication Number of cores and cross sectional area 2 x 0 75 mm2 Communication Communication protocol Connection type KNX TP galvanically isolated Bus load 5 mA Degree of protection Degree of protection Degree of protection acc to EN 60529 see mounting instruction IP54 Safety class Safety class acc ...

Page 9: ...g Dimensions 71 x 137 x 61 mm Suitable drive shafts Round shaft with centering element 8 16 mm 8 10 mm Square shaft 6 12 8 mm Min drive shaft length 30 mm Max shaft hardness 300 HV 1 The documents can be downloaded from http siemens com bt download Diagrams Internal diagrams The damper actuator is supplied with two prewired cables Dp G CE CE 1 1 2 G0 2 3547G01 Tool Power supply and communication c...

Page 10: ...heilerstrasse 1a 6300 Zug Switzerland Tel 41 58 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11753386_en _a Edition 2020 02 25 Dimensions Measurements in mm ...

Reviews: