Technical Instructions
GBB/GIB Series Non-spring Return, 24 Vac, Modulating Control
Document Number 155-176P25
June 22, 2015
Page 16
Siemens Industry, Inc.
Service
WARNING:
Do not open the actuator.
If the actuator is inoperative, replace the unit.
Troubleshooting
WARNING:
To avoid injury or loss of life, pay attention to any hazardous voltage (for example, 120 Vac)
when performing checks.
•
Check that the wires are connected correctly.
•
Check that offset (start point) and span are set correctly, if used.
•
Check that the direction of rotation switch matches the rotation of the damper shaft.
•
Connect wires 1 (red) and 2 (black) to a Digital Multimeter (DMM) with the dial set at Vac to
verify that the operating voltage is within range.
•
If the actuator is not working, check the damper for blockage. If blocked, remove the
obstacle and cycle the actuator power off and on. The actuator should resume normal
operating mode.
Dimensions
Figure 28. Dimensions of the ASK75.1U Weather Shield in Inches (Millimeters).
Figure 29. Dimensions of the ASK75.7U Weather Shield in Inches (Millimeters).