Siemens OOH941 Installation Instructions Manual Download Page 2

2

A6V10324659_en--_j

AIR CURRENTS

Before  a  detector  can  sense  a  fire,  the  products  of
combustion  or  smoke  must  travel  from  the  fire  to  the
detector.  This  travel  is  especially  influenced  by  air
currents;  therefore,  consider  air  movement  when
designing the system. While combustion products tend
to rise, drafts from hallways, air diffusers, fans, etc., may
help or hinder the travel of combustion products to the
detector.  When  positioning  a  detector  at  a  particular
location, give consideration to windows and doors, both
open and closed, to ventilating systems, both in and out
of  operation,  and  to  other  factors  influencing  air
movement. Do not install a detector in the air stream of
a  room  air  supply  diffuser.  It  is  better  to  position  a
detector closer to an air return.
The  distance  that products  of  combustion  or  smoke
travel from a fire to the detector is not usually the shortest
linear route. Combustion products or smoke usually rise
to the ceiling, then spread out. Average ceiling heights of
8 to 10 feet do not abnormally affect detector response.
High  ceilings,  located  in  churches,  warehouses,
auditoriums, etc., do affect detector response and should
be considered.

SPECIAL CEILING CONSTRUCTION FACTORS

Ceiling obstructions change the natural movement of air
and combustion products.  Depending on the direction of
smoke travel, joists and beams can slow the movement
of  heated  air  and  smoke,  while  pockets  between them
can contain a reduced level of smoke. Take obstructions
created by girders, joists, beams, air conditioning ducts,
or  architectural  design  into  consideration  when
determining  area  protection.  Refer  to  the  Initiating
Devices chapter of NFPA 72 for Location and Spacing
requirements  for  specific  types  of  construction;  e.g.
beam, suspended, level, sloped and peaked ceilings.

TEMPERATURE – HUMIDITY – PRESSURE – AIR
VELOCITY

The temperature range for the OOH941 detector is 32 °F
(0 °C)  to  120 °F  (49 °C).  Use  the  detector  in
environments  where  the  humidity  is  15 %  to  95 %  RH
continuous  non-condensing  and  1 %  to  99 %  for  short
duration (24 h to 48 h). Normal changes of atmospheric
pressure  do  not  affect  detector  sensitivity.  The  air
velocity  range  is  0-4000 ft/min  for  open  areas
applications.  Follow  detector  spacing and  location
requirements in NFPA 72 Chapter for High Air Movement
Areas and Control of Smoke Spread. The detectors can
also  be  installed  in  duct  applications  between  0  and
4000 ft/min.  For  duct  installations  follow  detector
installation  requirements  in  NFPA  90A,  Chapter  for
Special  Ceiling  Construction  Factors.  When  the
detectors  employ  a  fixed  temperature  rating  of  165 °F
(74 °C) or  less,  they  are  intended  for  a  maximum
installation temperature of 100 °F (38 °C).

LED INDICATOR OPERATION

The Model OOH941 contains an LED indicator capable
of  flashing  either  one  of  three  distinct  colors:  green,
yellow,  or  red.  The  microprocessor-based  detector
monitors the following:

·

  Smoke in its sensing chamber

·

  Smoke sensitivity is within the range indicated on the

nameplate label

·

  Internal sensors and electronics

Based on the results of the monitoring, the LED indicator
flashes the following:

Flash
Color

Condition

Flash  Interval

(Seconds)

Green *

Normal supervisory operation.
Smoke sensitivity  is within rated
limits.

10

Yellow

Detector is in trouble and needs
replacement.

4

Red

Alarm

1

No
Flashes *

Detector is not powered, or
replacement  is needed.

* LED can be turned off. Please follow the corresponding
description of the Panel used.

DETECTOR PROGRAMMING

Each  detector  must  be  programmed  to  respond  to  an
address between 001 – 252.

·

To  program  the  detector  address,  use  the  Model
DPU  Device  Programming  Unit.  Refer  to  the  DPU
Manual, P/N 315-033260.

·

  Record the loop and device number (loop address)

for the detector on the detector label and on the base
to prevent installing the detector in the wrong base.
The optional DPU label printer can be used for this
purpose.

Each detector provides pre-programmed parameter sets
which  can  be  selected  by  the  panel.  The OOH941
provides two different alarm channels: the multi-criteria
(UL268)  and  direct  in-duct  (UL268A)  channel  with
supplementary  heat  detection,  and  the  dedicated  heat
(UL521) channel. They can be used simultaneously and
configured  individually  by  the  panel. Follow  the
description  and  instructions  provided  in  the  operation
manual of specific control panel used. The OOH941 can
be  set  to  the  OOH941 Selectable  Application  Profiles,
OOH941  Selectable  Fixed  Temperature  Threshold
Profiles  and  OOH941 Selectable  Alarm  Threshold
Setting  Profiles  shown  in  the  tables  below  and  to  the
right.
Additionally, the detector can have another channel that
can  be  configured  by  the  panel  to  have  a  low  or  high
temperature  warning  in  the  range  from  -4  to  120 °F
(-20 to 49 °C).

Summary of Contents for OOH941

Page 1: ...s area is protected adequately by each smoke detector This is why it is mandatory to closely follow the installation drawings In all installations place the detector on the ceiling a minimum of 6 inches from a side wall or on a wall 12 inches from the ceiling For thermal detection use the matrix below Spacing Feet Temperature Rating F With without Guard Model 50 135 145 155 165 175 With and withou...

Page 2: ...hapter for High Air Movement Areas and Control of Smoke Spread The detectors can also be installed in duct applications between 0 and 4000 ft min For duct installations follow detector installation requirements in NFPA 90A Chapter for Special Ceiling Construction Factors When the detectors employ a fixed temperature rating of 165 F 74 C or less they are intended for a maximum installation temperat...

Page 3: ...sure that the panel supports Isolator mode for the OOH941 product version 30 Isolator mode must not be used with a OOH941 product version 30 You will find the product version number on the detector label DETECTOR MOUNTING The recommended orientation of the detector for wall mounting is shown in Figure 4 To ensure proper installation of the detector head into the base be sure the wires are properly...

Page 4: ...welding electrical arcing present Some airborne deceptive phenomena contaminant present Hospital Controlled clean environment High level risk Some exposure RF generating equipment Exposure to cleaning solvents Health Care Higher level risk relatively clean electronic equipment Some chemical and cleaning vapor exposure Dormitory Airborne dust and temperature changes living quarters Cooking fumes sm...

Page 5: ...shown after System reset which represents the non alarm condition OOH941 is a polarity insensitive detector Line 1 and Line 2 can be either line of the loop 5 NO C NC 6 SUPERVISED AND POWER LIMITED RELAY CONTACTS 3A 120 VAC 3A 30 VDC DO NOT USE AN END OF LINE DEVICE OPTIONAL REMOTE ALARM INDICATOR MODELS 8727W 8727C RL HW RL HC TO NEXT BASE TO NEXT BASE DO NOT USE AN END OF LINE DEVICE DETECTOR BA...

Page 6: ...e can enter the sensing chamber and alarm the control panel when the detector reaches the programmed obscuration concentration level The OOH941 detectors can also be tested individually using the DPU Refer to the DPU manual P N 315 033260 MAINTENANCE The control unit automatically indicates the trouble message for the OOH941 detector whose smoke chamber changes to the level where the set sensitivi...

Page 7: ... profiles settings are available and suitable for these and other applications See the table titled Selectable Application Profiles table in this document for options and application descriptions Failure to follow these guidelines may result in unwanted nuisance alarms Method to configure the detector s special application sensitivity The detector default sensitivity is for a standard office envir...

Page 8: ...rham Park New Jersey 07932 www siemens com buildingtechnologies Siemens Canada Limited Smart Infrastructure 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada Siemens Industry Inc Data and design subject to change without notice A6V10324659_en _j P N A5Q00044198 ...

Reviews: