background image

 Note: This instruction outlines recommended

installation procedure.

1. Turn OFF and lock out the power supplying the Safety

Switch.

2. Turn the Safety Switch OFF.

3.  Slide Neutral into left side of Line Base as shown in

Fig. 1.

Item:

Neutral Kit
Catalog Numbers HNC612, HNC623, HNC263

For use with:

60 - 100 Amp General Duty, 30 - 100 Amp

Heavy Duty VBII Safety Switches

Page 

of 

2

Pc. No.

500209C00

Installation Instructions for Neutral Kit

Fig. 1

s

©

 1999 Siemens Energy & Automation, Inc.

4. Secure neutral with screw provided, see Fig. 2 for

mounting and bonding locations. Torque to 30 lb.-ins.

5. Install conductors and torque wire connectors to the

values listed in the torque table on the interior labels.

6. When bonding is required, insert green thread rolling

screw and torque to 29 lb.-ins.

7. Close cover before supplying power to this switch.

SAFETY INSTRUCTIONS

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.
For questions call 1-800-241-4453 or our web site:
http://www.sea.siemens.com/dpd

Hazardous voltage.
Will cause death or serious
injury.

Turn off and lock out all power
supplying this Safety Switch
before installing kit.

Replace the covers and shields
before restoring power to switch.

Bonding

Fig. 2

Bonding

Bonding

Mounting
Screw

Mounting
Screw

30 Amp Heavy Duty

60 Amp General Duty

Neutral Kit HNC612

60/100 Amp Heavy Duty

100 Amp General Duty

Neutral Kit HNC623

NOTE: Installation of Neutral Kit Cat. No. HNC263 (100A,

200% Neutral) and Neutral Kit Cat. No. HNC623
are identical.

Reviews: