Siemens MXL Installation Instructions Download Page 2

Document No. 565-957
Installation Instructions
August 12, 2005

1. Follow all shutdown procedures necessary to

prevent damage to any equipment or harm to any
personnel.

2. Turn OFF power to the MEC/MBC/RBC enclosure.
3. In the MXL enclosure, locate the NIM-1R or

NIM-1W module (hereafter referred to as the
NIM-1 module). This module will be plugged into
the connectors on a MOM-2 or MOM-4 module. If
it is plugged into a MOM-4 module, note whether
the NIM-1 module is plugged into the slot closest
to the terminal block labeled TB3 or TB4.

4. If the NIM-1 is plugged into a MOM-2 module,

or if it is plugged into the slot closest to terminal
block TB4, the following instructions apply to
connections on TB4. If the NIM-1 module is
plugged into a MOM-4 module, in the slot closest
to TB3, the instructions apply to connections on
TB3.

5. Connect one end of the shielded twisted pair

cable to terminal 1 and 2 on the appropriate
terminal block, as speci

fi

ed above. Terminal 1

is the negative (-) terminal, and terminal 2 is
the positive (+) terminal. There is no terminal
available for the shield, so it will be connected at
the driver. (See Figure 1 and Figure 2.)

6. Connect a 120-ohm, 1/4 watt resistor between

terminals 3 and 4 of this same terminal block.
See Figure 2.

7. At the MEC/MBC/RBC, attach the +, -, and S

leads of the RS-485 cable to an FLN/PMD trunk
connector. Allow an additional 12 inches (305
mm) of cable before terminating to the connector.

The standard practice used by MXL
installers would also require a 120-ohm
resistor between terminals 1 and 2.
Do NOT install a resistor across these
terminals.

8. Turn ON power to the MEC/MBC/RBC enclosure.

9. Start any other equipment that might have been

shut down for this installation.

FLN

DRIVER

S

-

+

MXL PANEL

TAPE BACK

SHIELD

GW1326R1

RS-485 TRUNK CABLE

 (MAX 4000’/1219.2 m;

 STANDARD 24 AWG LOW CAPACITANCE)

1
2
3
4

TB3

or

TB4

NIM-1 MODULE

120 ohms

1/4 watt

resistor

Figure 1. Connecting the Siemens MXL Driver to the MXL System.

Page 2 of 4

Siemens Building Technologies, Inc.

Summary of Contents for MXL

Page 1: ...8DI 8DO 8AI 8AO point expansion support modem with HOA 986 83379G Siemens MXL Driver MEC with Ethernet BLN 8DI 8DO 8AI 8AO point expansion support HOA ready 986 83379H Siemens MXL Driver MEC with Ethernet BLN 8DI 8DO 8AI 8AO point expansion support with HOA Warning Caution Notations WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment da...

Page 2: ... on the appropriate terminal block as specified above Terminal 1 is the negative terminal and terminal 2 is the positive terminal There is no terminal available for the shield so it will be connected at the driver See Figure 1 and Figure 2 6 Connect a 120 ohm 1 4 watt resistor between terminals 3 and 4 of this same terminal block See Figure 2 7 At the MEC MBC RBC attach the and S leads of the RS 4...

Page 3: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Do NOT use GW0955R1 Figure 2 Connecting the Siemens MXL Driver to the MXL System The standard practice used by MXL installers would also require a 120 ohm resistor between terminals 1 and 2 Do NOT install a resistor across these terminals Siemens Building Technologies Inc Page 3 of 4 ...

Page 4: ...nts are introduced Product or company names mentioned herein may be the trademarks of their respective owners 2005 Siemens Building Technologies Inc Siemens Building Technologies Inc Your feedback is important to us If you have Document No 565 957 1000 Deerfield Parkway comments about this document please send Country of Origin US Buffalo Grove IL 60089 4513 them to SBT_technical editor siemens co...

Reviews: