Explanations to example (Figure 11, p. 85):
A: We have a transmitter with a measuring span of 0 to 16 bar. It should be set to a
measuring span of 2 to 14 bar. A reference pressure of 11 bar is available.
B: The current to be adjusted is first calculated for the desired start of scale (2 bar)
at the applied reference pressure using the formulae (Figure 10, p. 85). The cur-
rent to be adjusted is first calculated for the desired start of scale (2 bar) at the
applied reference pressure using the formulae.
C: The current to be adjusted is first calculated for the desired full scale (14 bar) at
the applied reference pressure using the formulae (Figure 10, p. 85) and then ad-
justed (16 mA).
Figure 10 Formula for calculating the current (start of scale, full scale)
A
Output simulation
B
Calculate start of scale
C
Calculate end of scale
Given: p
Ref
= 11 bar
The measuring span 2 - 14 bar is to be adjusted
Figure 11 Example: adjusting start of scale and full scale
Current to be ad-
justed at MA
Current to be ad-
justed at ME
I = output current
p = applied reference pressure
nom
Ref
I =
* 16 mA + 4 mA
p - MA
ME - MA
Ref
nom
act
I =
* 16 mA + 4 mA
p - MA
ME - MA
nom
nom
nom
Ref
nom
act
ME
act
= old full scale
MA
act
= old start of scale
ME
nom
= new full scale
MA
nom
= new start of scale
p
16
20 mA
4
adjust
0
11
16 bar
14
2
MA
ME
MA
nom
nom
act
13
18
4
adjust
0
11
16 bar
2
MA
MA
ME
nom
act
act
4
15
20 mA
0
11
16 bar
Ref
Current to be ad-
justed at MA
current to be ad-
justed at ME
nom
nom
I =
* 16 mA + 4 mA = 13 mA
11 bar - 2 bar
16 bar - 0 bar
p
Ref
I =
* 16 mA + 4 mA = 16 mA
11 bar - 2 bar
14 bar - 2 bar
p
Ref
Summary of Contents for MS Series
Page 2: ......
Page 4: ...SITRANS P Serie MS 4 C79000 B5674 C40 04 ...
Page 10: ...SITRANS P Serie MS 10 C79000 B5674 C40 04 ...
Page 16: ...SITRANS P Serie MS 16 C79000 B5674 C40 04 Technische Beschreibung ...
Page 50: ...SITRANS P Serie MS 50 C79000 B5674 C40 04 Inbetriebnahme ...
Page 51: ...SITRANS P Serie MS 51 C79000 B5674 C40 04 Technische Daten 7 Siehe folgende Seiten ...
Page 56: ...SITRANS P Serie MS 56 C79000 B5674 C40 04 Pflege und Wartung ...
Page 60: ...SITRANS P Serie MS 60 C79000 B5674 C40 04 Zertifikate ...
Page 66: ...SITRANS P Serie MS 66 C79000 B5674 C40 04 Index ...
Page 72: ...SITRANS P MS series 72 C79000 B5674 C40 04 ...
Page 78: ...SITRANS P MS series 78 C79000 B5674 C40 04 Technical Description ...
Page 112: ...SITRANS P MS series 112 C79000 B5674 C40 04 Commissioning ...
Page 113: ...SITRANS P MS series 113 C79000 B5674 C40 04 Technical Data 7 See following pages ...
Page 118: ...SITRANS P MS series 118 C79000 B5674 C40 04 Maintenance and Care ...
Page 122: ...SITRANS P MS series 122 C79000 B5674 C40 04 Certificates ...
Page 128: ...SITRANS P MS series 128 C79000 B5674 C40 04 Index ...
Page 129: ......