Parameters
12.8 Batch Control (P560 – P568)
BW500 and BW500/L
Operating Instructions, 12/2016, A5E33482052-AD
177
12.8.2
P564 Batch Setpoint
Sets the batch total. When the amount of material delivered reaches this point, the batch relay
contact opens (P100) to signal the end of the batch. (
f
= 0.000).
Enter the setpoint of the units of weight selected (P005).
Note
The batch setpoint can be modified while in RUN mode using the up/down arrow keys.
12.8.3
P566 Batch Pre-Warn
Enables or disables the pre-warn function associated with batch control, warning that the batch
is nearing completion.
Entry:
0 =OFF
f
1 = ON
12.8.4
P567 Batch Pre-Warn Setpoint
Sets the setpoint for the pre-warn function (P566). When the batch reaches the setpoint, the
relay contact associated with the pre-warn function (P100) closes (
f
= 0.000).
Enter setpoint in units of weight selected (P005).
12.8.5
P568 Batch Pre-Act
Acts on the batch operation such that when the batch totalizer is reset, the batch total is
compared to the setpoint (P564). The difference is then applied to pre-act on the setpoint for the
next batch to improve the accuracy of the batch. The activity is internally limited to ±10% of the
batch setpoint.
Entry:
0 = OFF
f
1 = Auto
2 = Manual
e.g. For Auto Batch Pre-Act
1st batch
2nd batch
3rd batch
setpoint
1000
1000
1000
pre-act
1000
950
960
total
1050
990
1000
Summary of Contents for Milltronics BW500
Page 1: ...Operating Instructions Milltronics BW500 and BW500 L 12 2016 Edition Integrators ...
Page 12: ...Table of contents BW500 and BW500 L 10 Operating Instructions 12 2016 A5E33482052 AD ...
Page 14: ...Safety Notes BW500 and BW500 L 12 Operating Instructions 12 2016 A5E33482052 AD ...
Page 16: ...The Manual BW500 and BW500 L 14 Operating Instructions 12 2016 A5E33482052 AD ...
Page 48: ......
Page 154: ......
Page 218: ...Index BW500 and BW500 L 216 Operating Instructions 12 2016 A5E33482052 AD ...
Page 219: ......