background image

Maintenance Info MI291a: Guarto MP3 SR2 

1.2 

Fixed Application Problems 

 

The current RTC chip is not available anymore. So, a new pin compatible device 
with a new chip was produced in cooperation for Guarto and AlgoRex. This re-
quires the use of a new RTC driver, which supports the current chip as well as the 
new device. 
Therefore, a new HW version is provided too, where the current RTC chip is re-
moved from the board and a socket is mounted instead, so that the piggy-back de-
vice with the new RTC chip can be inserted. 
 

1.3 

Fixed Tool Problems 

 

For the mentioned SR1 of MP3 an improved SWE6 tool V5.0a was provided. 
 
The following problems were fixed: 

z

 

The delay of remote transmission for 'Security-jeopardizing fault' and 'Major fault' 
was not visible and configurable anymore  
(new range for each remote transmission type 10..1800s) 

z

 

Generation of CNAP profile adjusted that a data import of the management sys-
tem doesn't stop anymore because of a section without zone 

z

 

Listing of configuration data (for sections) contained also the section number 
and not only the numbers of the linked zones 

 

Installation (Update V5.0): 

– 

Uninstall SWE6 MP3 V5.0 

– 

Install SWE6 MP3 V5.0 

Î

 

When this message appears: click No 

 

 

 
 
 
 

4

 

Building Technologies

 

 MI291a.doc

Fire Safety & Security Products 

 

01.2009

 

 

Summary of Contents for MI291A

Page 1: ...Guarto Multifunctional Security System Maintenance Info MI291a MP3 Service Release SR2 Building Technologies Fire Safety Security Products ...

Page 2: ...übergeben worden ist We reserve all rights in this document and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was deliv...

Page 3: ...e new RTC chip device 1 1 Actual Compatibility Guarto MP3 SR2 Version Memories Remark Checksum Actual compatibility Software Tool V5 0a Maintenance System SWE6 Release MP3 SR1 V4 4 Standard Text Editor SWU6 Release MP3 Master Card E3X130 CCD005 03 Control Unit Program Empty EPROM Type 27C4001 part No 476 362 0001 0AE2 odd 0D1E even Bridges EPROM X11 Y12 RAMs RAM 512kx8 part no 484 794 Bridges RAM ...

Page 4: ...roblems For the mentioned SR1 of MP3 an improved SWE6 tool V5 0a was provided The following problems were fixed z The delay of remote transmission for Security jeopardizing fault and Major fault was not visible and configurable anymore new range for each remote transmission type 10 1800s z Generation of CNAP profile adjusted that a data import of the management sys tem doesn t stop anymore because...

Page 5: ......

Page 6: ...ding Technologies Group International Headquarters Fire Safety Security Products Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com Document no A6V10235243 Manual CS6 Edition 01 2009 Section 2 ...