background image

Maintenance Info MI290a: Guarto MP3 SR1 

1.2 

Fixed Application Problems 

 

A CT6C configured for ‘Section operation’ does not crash the system anymore. 
The internal workspace for the terminal application is now increased so that the 
function has enough memory available. 
 
A wrong indication “not done” for the execution of a command has been eliminated. 
This was just indicated for a Section with Exit-Route when it was switched on, in 
case the configuration did allow switching off/on the sensors. 
 
For the private devices CT6C and DCU6 on the LON bus, the communication has 
been enhanced. Now the supervision is stable so that random connection tamper 
messages will be avoided. 
 

1.3 

Improvements for Management Station 

 

The stability of the communication is improved for the connection of management 
stations. In fact, a correction in the MM8001 allows now to connect two such sta-
tions with Guarto. 
 
New properties are supported in the communication model, which were added in 
the application of MP3. They are now available on the interface, but have not been 
added to the exported data in the profiles (due to incompatibility in import). 

z

 

‘Door’ object for access control 

– 

doorOpen 

 

 

a door is currently open 

– 

doorUnlocked  

 

a door is currently released 

z

 

‘Area’ object 

– 

initialPINs 

 

 

user(s) have not yet changed the default PIN 

– 

inhibitionTimeNotActive  

z

 

‘Terminal’ object 

– 

operationFree  

 

a terminal is enabled for operation 

 

 

 

 

e.g. only by key (without a user PIN) 

z

 

‘PowerSupply’ object 

– 

tamperEmergencyPower 

possible attack by running out of power 

– 

faulty  

 

 

indicates a problem from the attached ADI  

 

   (MBus 

addressing 

unit) 

 

1.4 Known 

Problems 

 

Guarto: Communication with management stations: 

– 

The protection for the time synchronization via network is too restrictive. There is 
currently no way for correcting errors from remote (e.g. wrong daylight saving 
time). Local access is necessary to put CS6 in Service-Mode. 

 
SWE6-Tool: Configuration and data export: 

– 

The dialogues are missing in the Area for setting the delay times of the remote 
transmission of ‘Security-jeopardizing-faults’ and ‘Major-fault’ (default = 120s!). 

– 

The Profile-Generator does not put virtual Sections (without Zones) into the pro-
files. 

Æ

 Workaround: attach a dummy Zone (linked to ADI) getting both entries. 

 
Mind the improved SWE6 tool V5.0a which became available in March 2005. 
 
 

4

 

Building Technologies

 

 MI290a.doc

Fire Safety & Security Products 

 

01.2009

 

 

Summary of Contents for MI290A

Page 1: ...Guarto Multifunctional Security System Maintenance Info MI290a MP3 Service Release SR1 Building Technologies Fire Safety Security Products ...

Page 2: ...übergeben worden ist We reserve all rights in this document and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was deliv...

Page 3: ...re Tool V5 0 Maintenance System SWE6 Release MP3 V5 0a Maintenance System SWE6 Release MP3 SR1 V4 4 Standard Text Editor SWU6 Release MP3 Master Card E3X130 CCD005 02 Control Unit Program Empty EPROM Type 27C4001 part No 476 362 0001 5200 odd 8E00 even Bridges EPROM X11 Y12 RAMs RAM 512kx8 part no 484 794 Bridges RAM X10 LON Adapter K3I070 BKD002 02 Empty EPROM Type 27C256 part No 390 477 BC00 Ter...

Page 4: ...ofiles due to incompatibility in import z Door object for access control doorOpen a door is currently open doorUnlocked a door is currently released z Area object initialPINs user s have not yet changed the default PIN inhibitionTimeNotActive z Terminal object operationFree a terminal is enabled for operation e g only by key without a user PIN z PowerSupply object tamperEmergencyPower possible att...

Page 5: ...Maintenance Info MI290a Guarto MP3 SR1 5 Building Technologies MI290a doc Fire Safety Security Products 01 2009 ...

Page 6: ...ding Technologies Group International Headquarters Fire Safety Security Products Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com Document no A6V10235239 Manual CS6 Edition 01 2009 Section 2 ...

Reviews: