Installation Instructions  

July 30, 2008 

 

Using the HOAs Before Start-up 

If the HOAs are required for equipment control 
before the MEC start-up is performed, perform the 
following procedure to set the analog point jumpers. 

 

CAUTION: 

 

Always wear an electro-static discharge 
wrist strap and discharge accumulated 
static before touching field panel 
components. 

NOTE: 

The jumpers are shipped in the Voltage (V) 
position. The jumpers must remain in this 
position when they are not being used. 

1.  With an ESD wrist strap attached to your wrist 

and a good earth ground, remove the MEC 
front cover. See Figure 2. 

2.  Set the jumpers on the termination board to the 

desired physical point type for the analog input 
(AI) and analog output (AO) points. See Figure 
3 for the jumper positions. 

3.  If required, install the MEC 100K Thermistor 

jumper on the lower left pins of each analog 
input point that is monitoring a 100K thermistor. 
See Figure 3 for the jumper positions.  

For more information, see the 

MEC 100K 

Thermistor Option Kit Installation Instructions

 

(586-679). 

4.  Connect the HOA switch cable. 

5.  Replace the MEC front cover. 

The HOAs may now be used to control equipment. 

HOA Status LEDs 

For MECs with HOA switches, a green LED is 
located below the HOA switches. The LED flashes 
after start-up, indicating that the switches are in the 
AUTO position and are functioning correctly.  

If any control switch is moved out of AUTO, the light 
stops flashing and remains on. 

 

Siemens Building Technologies, Inc. 

Page 5 of 6

 

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for MEC 1100

Page 1: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Page 2: ...puts can be placed into AUTO control and nine manual control positions For more information on MEC hardware and applications see the Modular Equipment Controller Owner s Manual 125 2183 Product Numbers MEC Models with RS 485 ALN Direct Connect and Auto Dial 549 610 MEC Model 1100 HOA Ready 549 611 MEC Model 1101 HOA Not available 549 612 MEC Model 1110 HOA Included 549 613 MEC Model 1200 EXP HOA R...

Page 3: ... Expected Installation Time 20 minutes NOTE Additional tasks for example running power wiring may add to your installation time Refer to the estimating tool for more information Prerequisites All necessary wiring is pulled If mounting in an MEC or PX series enclosure MEC or PX series enclosure installed Either the 115V or 230V service box kit or the 192 VA or 384 VA service box assemblies are inst...

Page 4: ...of the four mounting holes 2 Using the mounting ears on the back of the controller as a template mark the position of the four mounting holes on the surface 3 Start the screws provided with the enclosure in the perforated backplane 3 Drill the four mounting holes or start the screws into the marked template holes 4 Place the MEC on the backplane of the enclosure so that the mounting ears rest on t...

Page 5: ... 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 MEC0011R1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 MEC0114R1 VOLTAGE CURRENT VOLTAGE CURRENT RTD JUMPER POSITIONING GUIDE FOR ANALOG OUTPUT ANALOG INPUT CONNECTORS ANALOG OUTPUT CONNECTORS JUMPER POSITIONING GUIDE FOR ANALOG INPUT JUMPER SET TO FOUR UPPER PINS VERTICAL CONTACTS PLUG SET TO TWO LOWER LEFT PINS JUMPERS JUMPERS Figure 2 Removing the MEC...

Page 6: ... the analog input AI and analog output AO points See Figure 3 for the jumper positions 3 If required install the MEC 100K Thermistor jumper on the lower left pins of each analog input point that is monitoring a 100K thermistor See Figure 3 for the jumper positions For more information see the MEC 100K Thermistor Option Kit Installation Instructions 586 679 4 Connect the HOA switch cable 5 Replace ...

Page 7: ... mentioned herein may be the trademarks of their respective owners 2008 Siemens Building Technologies Inc Siemens Building Technologies Inc 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 USA Your feedback is important to us If you have comments about this document please send them toSBT_technical editor us sbt siemens com Document No 586 146 Country of Origin US Page 6 of 6 Artisan Technology ...

Page 8: ...l service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE INSPECTION Remotely inspect equipment before purchasing with our interactive website at www instraview com LOOKING FOR MORE INFORMATION Visit us on the web at www artisantg com for more information on ...

Reviews: