2.3.3
Heating
Inputs and outputs
Table 2-8
No.
Hardware
LOGO! module
Program inputs/outputs
1. PT100 temperature sensor
Master RTD A1
AI3
2. PT1000 temperature sensor
Master RTD A2
AI4
3. Heating room 1 on/off
Master DM8 Q1
Q14
4. Heating room 2 on/off
Master DM8 Q2
Q13
Function description
With the LOGO! display and LOGO! TDE it is possible to set a setpoint value for
each room.
If the room temperature reaches the setpoint value, the heating is switched off.
If the room temperature falls 1° below the setpoint value, the heating is switched on
again.
Table 2-9
No.
Function
Function block
Block name in the
program
1.
Temperature-dependent on/off heating 1
Analog Comparator
heater 1
2.
Temperature-dependent on/off heating 2
Analog Comparator
heater 2
Note
In the LOGO! basic device (master), the standard setting for two analog inputs
are used so the RTD expansion module has the inputs AI3 and AI4.