Technical data
(continued)
Flame supervision with ionization probe
At mains voltage
Values apply to factory setting of parameters 182 = 0
120 V AC
230 V AC
Detector voltage between ionization probe and ground
Approx. 270 V AC
Approx. 270 V AC
(AC voltmeter Ri
″10 Mς)
Switching threshold (limit values):
Switching on (flame ON) (DC ammeter Ri
′5 kς)
″DC 1.5 µA
″DC 1.5 µA
Switching off (flame OFF) (DC ammeter Ri
′5 kς)
′DC 0.5 µA
′DC 0.5 µA
Detector current required for reliable operation
″DC 3 µA
″DC 3 µA
Switching threshold in the event of poor flame during operation
Approx. DC 2 µA
Approx. DC 2 µA
(LED flashes green)
Possible detector current with flame (typical)
20 µA DC
20 µA DC
Flame supervision with UV flame detector QRA2 / QRA2M /
At mains voltage
QRA4 / QRA4M / QRA10 / QRA10M
Values apply to factory setting of parameters 182 = 0
120 V AC
230 V AC
Detector voltage at QRA2 / QRA2M / QRA4 / QRA4M / QRA10 /
QRA10M (with no load)
Terminal 6 OFF (test mode)
Approx. 290 V AC
Approx. 290 V AC
Terminal 6 ON (operating mode)
Approx. 250 V AC
Approx. 250 V AC
Switching threshold (limit values):
Switching on (flame ON)
″20 µA DC
″20 µA DC
Switching off (flame OFF)
′5 µA DC
′5 µA DC
Detector current required for reliable operation
″24 µA DC
″24 µA DC
Switching threshold in the event of poor flame during operation
Approx. 24 µA DC
Approx. 24 µA DC
(LED flashes green)
Possible detector current with flame (typical):
Test mode
700 µA
700 µA
Operating mode
550 µA
550 µA
Flame supervision with photocell detector RAR9
At mains voltage
Values apply to factory setting of parameters 182 = 0
120 V AC
230 V AC
Switching threshold (limit values):
- Switching on (flame ON)
″6.5 µA DC
″6.5 µA DC
- Switching off (flame OFF)
′3.5 µA DC
′3.5 µA DC
Detector current required for reliable operation
″10 µA DC
″10 µA DC
Switching threshold in the event of poor flame during operation
Approx. 10 µA DC
Approx. 10 µA DC
(LED flashes green)
Possible detector current with flame (typical)
65 µA DC
65 µA DC
Possible detector current in the event of glare, e.g., with artificial
70 µA DC
70 µA DC
light (leads to lockout with error message LOC10)
The detector current values specified in the table only apply to the factory settings and under the
following conditions:
- Mains voltage 120 V AC / 60 Hz or 230 V AC / 50 Hz, depending on type
- Ambient temperature 23 °C
- Parameter 182 in accordance with the factory setting from the following table
20/40
Building Technologies CC1N7782en 18.04.2018