11/19
Building Technologies
CC1N7461en
21.08.2018
Basic diagram
P (R)
1
EK2*
16
15
14
13
QRA...
+
ION
12
L2
17
M2
M
~
11
GV3
7
10
5
6
GV2
(GV)
GV1
Z
N (Mp)
2
18
19
P
P
LP
T
T
GP
W
R1
8
9
4
3
N
M
~
M1
(11)
22
21
LK
N
~
20
a
z
br1
b
a
ar1
ar3
EK1*
a
b
fr2
b
a
FR
a
NTC
VIII
IX
XIII
VIII
IX
XI
fr1
b a
b
b
b
a
b
a
AR
br2
BR
b
a
ar2
UL1
L1
SM
X
XI
II
IV
VII
I
V
XII
IV
VI
III
7461a01/0207
SB
AS
When using UV flame detector QRA..., terminal 13 must be earthed.
Attention!
Do not press lockout reset button (EK...) for more than 10 seconds!
AR
Load relay with contacts «ar...»
LF
UV flame detector QRA...
AS
Unit fuse
LP
Air pressure switch
BR
Lockout relay with contacts «br...»
L1
Lockout warning lamp (built-in)
BS...
Operating switch
L2
Lockout warning lamp (external)
c
Fan contactor with contacts «c...»
M...
Fan
d
Auxiliary relay with contacts «d...»
NTC
Delay element (negative temperature coefficient)
e
Thermal overload contact
OV...
Oil valve
EK1
Lockout reset button on the burner control
QRA...
UV flame detector
EK2
Remote lockout reset button
R, R1
Control thermostat or pressurestat
ION
Ionization probe
R2
Load controller
FR
Flame relay with contacts «fr...»
RV
Control valve
FW
Flame supervision
SB
Safety limiter
GP
Gas pressure switch
SM
Synchronous motor of the sequence switch
GV...
Gas valve
SQ...
Air damper actuator (type reference)
(GV)
Gas valve for a pilot burner that is switched off after
UL1
Operating switch of the sequence switch motor
the second safety time
(can only be accessed when housing cover is
H
Main switch
removed)
LK
Actuator with end or auxiliary switches
W
Temperature or pressure limiter
a = actuator travels to the fully open position
Z
Ignition transformer
(maximum amount of air)
*
Do not press lockout reset button «EK...» for more than
z = actuator travels to the fully closed position
(min. amount of air)
10 seconds!
Legend