Standards and certificates
Only in combination
with the flame detector
Applied directives:
Directive for gas appliances
Directive for gas-fired appliances (only LFE10)
Directive for pressure devices
Electromagnetic compatibility EMC (immunity) *)
2006/95/EC
2009/142/EC
97/23/EC
2004/108/EC
*) The compliance with EMC emission requirements must be checked after the flame safeguard is
installed in equipment
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic burner control systems for oil burners
DIN EN 230
Only LFE10:
DIN EN
Automatic burner control systems for burners and appliances
298:2004
burning gaseous or liquid fuels
Automatic electrical controls for household and similar use
DIN EN 60730-
Part 2-5: Particular requirements for automatic electrical burner
2-5
control systems
The relevant valid edition of the standards can be found in the declaration
of conformity!
EAC Conformity mark (Eurasian Conformity mark)
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
With
LEC1…
LAE10
●
●
●
●
---
●
---
LFE10
●
●
●
---
●
●
●
Life cycle
Flame safeguards has a designed lifetime* of 250,000 burner startup cycles which,
under normal operating conditions in heating mode, correspond to approx. 10 years
of usage (starting from the production date given on the type field).
This lifetime is based on the endurance tests specified in standard EN 230 / EN
298. A summary of the conditions has been published by the European Control
Manufacturers Association (Afecor) (
www.afecor.org
).
The designed lifetime is based on use of the flame safeguards according to the
manufacturer
’s Data Sheet. After reaching the designed lifetime in terms of the number
of burner startup cycles, or the respective time of usage, the flame safeguards is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
4/15
Building Technologies Division
CC1N7781en
01.08.2016