GAMMA
instabus
Technical Product Information
December 2014
IP Control Center N152
5WG1 152-1AB01
Siemens AG
N 152, 4 Pages
Technical Manual
Infrastructure & Cities Sector, Building Technologies
Control Products and Systems
ã
Siemens AG 2014
Update: http://www.siemens.de/gamma
P. O. Box 10 09 53, D-93009 Regensburg
Subject to change wihout further notice
2.11.1.15/3
Environmental specifications
·
Climatic conditions: EN 60721-3-3 class 3k5
·
Ambient temperature in operation: -5 °C ... + 45
°
C
·
Storage temperature: - 25 ... + 70
°
C
·
Relative humidity (non-condensing): 5% to 93%
Marking
• KNX
EIB
CE mark
Complies with the EMC regulations (residential and func-
tional buildings) and low voltage regulations.
Location and Function of the Display and Op-
erating Elements
Figure 1: Location of the display and operating elements
A1 DC 24 V bus connector terminal (yellow-white)
A2 KNX bus connector terminal (black-red)
A3 Ethernet RJ45 socket
A4 KNX programming LED
A5 KNX learning button
A6 ERR: Error status LED
A7 LK: Ethernet Ac Communication LED
The device connections and the elements needed for
KNX commissioning - learning button and programming
LED - are accessible in the distribution board only when
the lid is removed.
Mounting and wiring
General description
The N-system DIN-rail device can be installed in distribu-
tion boards, surface or flush mounted, or on any DIN rail
complying with EN 60715-TH35-7,5.
The connection to the bus line is established via the bus
connector terminal (red-black) on the top side.
The RJ45 socket on the device front side provides the
connection to the Ethernet-IP data network.
Mounting
-
Snap the IP Control Center N152 (Figure 2, B1) on to
the DIN rail (Figure 2, B2).
-
Connect the auxiliary power DC 24 V with the yellow-
white bus connector terminal (Figure 1, A1).
-
Connect the bus line with the black-red bus connector
terminal (Figure 1, A2).
-
Plug an Ethernet patch cable with an RJ45 plug into
the RJ45 socket (Figure 1, A3) to connect the device
with the LAN/Intranet.
A connection is established to the network when the
yellow LED marked LK (Figure 1, A7) is continuously
lit.
Dismounting
-
Unplug the Ethernet patch cable from the RJ45 socket
(Figure 1, A3)
-
Remove the yellow-white bus connector terminal (Fig-
ure 1, A1) from its socket.
-
Remove the black-red bus connector terminal (Figure
1, A2) from its socket.
-
Remove the device (Figure 2, C1) with the catcher
(Figure 2, C3) from the DIN rail (Figure 2, C2)
B1
C1
C2
C3
B2
Figure 2: Mounting and dismounting a DIN-rail device
Slipping off bus connection blocks (Figure 3)
-
The bus connection block (Figure 3, D2) is situated on
the top of the device (Figure 3, D1).
-
The bus connection block (Figure 3, D2) consists of
two components (Figure 3, D2.1 and D2.2) with four
ERR
LK