Configuration and operation
4.5 Configuration with STEP 7 Basic / Professional
IE/PB LINK PN IO
Operating Instructions, 11/2017, C79000-G8976-C393-02
57
4.5
Configuration with STEP 7 Basic / Professional
4.5.1
Configuring the LINK
Creating the LINK and assigning the mode
For addressing the LINK the first time and configuring it you require STEP 7 Basic / STEP 7
Professional.
For the version and required support package, refer to the section Requirements for use
(Page 19).
Note
Operation in compatibility mode
You can operate the LINK with a compatible setting to the previous version
(6GK1 411-5AB00).
For operating the LINK in the compatibility mode, refer to the manual /2/ (Page 90) of the
previous version 6GK1 411-5AB00.
For the configuration, follow the steps below:
1.
Create a STEP 7 project.
2.
Insert a LINK from the catalog:
"Network components" > "Gateways" > IE/PB Link PN IO > 6GK1 411-5AB10
For the further configuration as a PROFINET I/O proxy, refer to the section Use as a
PROFINET IO device (Page 57).
For the further configuration as a gateway, refer to the section Use only as a gateway in
standard operation (Page 59).
Note
Support during configuration: Online help
The information system of STEP 7 will provide you with detailed information on the
procedure.
4.5.2
Use as a PROFINET IO device
Configuring the LINK as a PROFINET IO device.
The following is required for further configuration: You have created a project with the LINK,
see section Configuring the LINK (Page 57).