MOUNTING

(See Figure 10)

1. Use a standard 3 

1

/

2

-inch deep, double

gang electrical switchbox or a 4-inch
square electrical box that is 2 

1

/

2

 inches

deep with either a 1 

1

/

2

-inch deep

extension or a 1 

1

/

-inch deep plaster ring

extension.

2. Connect the field wiring. Insert the ICP-B6

into the box and fasten the module plate
to the box.

Figure 10

Mounting the ICP-B6

NOTE:

When using the double gang
switchbox or the plaster ring
extension, use the same four
screws to fasten both the mod-
ule and the blank plate (user
supplied).

3. Cover the module front plate with a 4-inch

blank plate (user supplied) and fasten
with two plate screws.

P/N 315-095306-10

Siemens Industry, Inc.

Building Technologies Division

Florham Park, NJ

Siemens Building Technologies, Ltd.

Fire Safety & Security Products

2 Kenview Boulevard

Brampton, Ontario

L6T 5E4 Canada

Summary of Contents for ICP-B6

Page 1: ... can be used as an independent remotely located telephone zone a speaker zone 25V or 70 7V RMS or notification appliance circuit NAC depending on how it is configured It communicates through the analog loop of the MXL MXLV System OPERATION Up to 12 ICP B6s can connect to each analog loop of the MXL MXLV These modules must be connected to the first 12 address locations on the analog loop The 24 VDC...

Page 2: ... 67 2 33 2 00 1 67 1 00 1 2 93 2 83 2 67 2 50 2 33 2 00 5 2 96 2 92 2 83 2 75 2 67 2 50 MAXIMUM LOOP RESISTANCE FOR EACH ICP B6 ON RISER NOTES 1 Resistances specified are for both wires 2 If higher currents are required Siemens Industry Inc recommends using a local auxiliary supply which is UL listed for fire protection signaling use The supply should be rated between 24 and 27 3 VDC When used as ...

Page 3: ...ILTERED FULL WAVE RECTIFIED 1 5A POWER LIMITED ICP B6 ICP B6 PROGRAM PLUG PROGRAM PLUG TB2 TB1 TB1 6 6 6 5 5 5 4 4 4 3 3 3 2 2 2 1 1 1 ANALOG LOOP CONNECTION SUPERVISED MODULE INPUT SUPPLY FROM PS 35 PSR 1 OR UL LISTED POWER SUPPLY MANUFACTURED BY ALARM SAF Model BN4 002 UL ELECTRICAL INPUT DC SUPPLY SUPERVISORY OUTPUT ACTIVATED JP2 JP2 JP1 JP1 EARTH SHIELD TB2 6 5 4 3 2 1 EARTH SHIELD Figure 1 An...

Page 4: ...4 Figure 4 ICP B6 Connections Using PSR 1 Figure 3 ICP B6 Connections When Using TRI 60 B6 ...

Page 5: ...AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION RISER NOMINAL VOLTAGE MAXIMUM CURRENT 17 5 VDC 175 mA 10K 1 2W 5 EOL RESISTOR P N 140 112172 AT LAST FJ 303 5 6K 1 2W 5 EOL RESISTOR ELECTRICAL INPUT DC SUPPLY SUPERVISORY OUTPUT ACTIVATED OUTPUT 20 5 TO 30 VDC 18mA MAX 8V 8mA 11V 70mA SUPERVISED POWER LIMITED FROM MXL MMB OR ALD 2I ON MOM 4 12 MAX ICP B6 MODULES PER LOOP SUPERVISED NOTES 1 TH...

Page 6: ...o input comes from the amplifier via the ASC 2 Amplifier Supervision card The ASC 2 supervises the audio con nection path to the ICP B6 and provides up to 100 watts of power The ASC 2 can be used as Style Y Class B or Style Z Class A Refer to the ASC 2 Instructions P N 315 092085 When the ICP B6 is used as a speaker zone the output speaker lines are supervised and power limited The audio output ca...

Page 7: ...ARTH TB2 6 5 4 3 2 1 SHIELD EARTH TB2 6 5 4 3 2 1 SHIELD EARTH ASC 2 ASC 2 15K 1 2W 5 EOL RESISTOR P N 140 820400 15K 1 2W 5 EOL RESISTOR P N 140 820400 15K 1 2W 5 EOL RESISTOR P N 140 820400 STYLE Z SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 9 VDC 0 5 mA ACTIVATED 25 VRMS 35 W MAX STYLE Y SUPERVISED SPEAKER ZONE CONNECTIONS SUPV 9 VDC 0 5 mA ACTIVATED 25 VRMS 35 W MAX 16 16 17 17 18 18 19 19 24K 1 ...

Page 8: ...e plate to the box Figure 10 Mounting the ICP B6 NOTE When using the double gang switchbox or the plaster ring extension use the same four screws to fasten both the mod ule and the blank plate user supplied 3 Cover the module front plate with a 4 inch blank plate user supplied and fasten with two plate screws P N 315 095306 10 Siemens Industry Inc Building Technologies Division Florham Park NJ Sie...

Reviews: