Siemens HZM Installation Instructions Manual Download Page 2

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-034850-8

2

INSTALLATION

Remove all system power before installation, first battery then AC. (To power up,

connect the AC first, then the battery.)

Electrical Connections

After you have set the HZM address, connect the field wiring. There are three basic
connections to the HZM: initiating devices, DLC or FS-DLC device loop, and 24 VDC
power. All terminals are power limited.

Initiating Devices

(Figures 2, 3, and 4)

The HZM supports one zone of initiating devices in either Class A or Class B. The
initiating devices are connected to terminals 5–8 on the HZM terminal block.  The
HZM is a polarity insensitive module and terminals 1 and 2 can be connected to
either line of the DLC or FS-DLC Device Loop. Figure 2 shows the Class A wiring.
Figure 3 shows the Class B wiring.

1

2

3

4

5

6

7

8

9

EARTH

DEVICE LOOP

24VDC POWER

LINE 2

LINE 1

STYLE D/CLASS A

(DCLA)

EOL * 

*  EOL DEVICE IS 4.7K, 1/4W (P/N 140-820188)

 FOR CANADIAN APPLICATIONS, USE MODEL 

   EL-33 WITH 4.7K, 1/4W RESISTOR.

+

+

+

Figure 2

HZM Initiating Devices Wiring Diagram

Class A/Style D (ULC DCLA) Installation

Figure 3

HZM Initiating Devices Wiring Diagram

Class B/Style B (ULC DCLB) Installation

DEVICE LOOP

24VDC POWER

LINE 2

LINE 1

1

2

3

4

5

6

7

8

9

EARTH

NOT USED

STYLE B/CLASS B

(DCLB)

* EOL DEVICE IS 4.7K,
  1/4W (P/N 140-820188)

 FOR CANADIAN APPLICATIONS,

   USE MODEL EL-33 WITH 
   4.7K, 1/4W RESISTOR.

+

+

EOL* 

NOTES
1. Wire 18 AWG minimum, 12

AWG maximum, 35 ohms Max.

2. Supervised, power limited to

NFPA 70 per NEC 760.

3. Voltage 24VDC.
4. Positive and negative ground

fault detected at <60K ohms
for terminals 5-8.

NOTES
1. Wire 18 AWG minimum, 12

AWG maximum, 35 ohms Max.
(both sides)

2. Supervised, power limited to

NFPA 70 per NEC 760.

3. Voltage 24VDC.
4. Positive and negative ground

fault detected at <60K ohms
for terminals 5, 8.

Summary of Contents for HZM

Page 1: ... Quick Start Manual P N 315 033875 or the FS 250 Programming Manual P N 315 049403 as applicable The alarm verification configuration is used only for non shorting detectors The HZM supports Class A and Class B wiring The module uses one address on the device loop It does not require any mechanical address programming Use the DPU Device Programming Unit to program and test the module HZM HZM FRONT...

Page 2: ...ows the Class B wiring 1 2 3 4 5 6 7 8 9 EARTH DEVICE LOOP 24VDC POWER LINE 2 LINE 1 STYLE D CLASS A DCLA EOL EOL DEVICE IS 4 7K 1 4W P N 140 820188 FOR CANADIAN APPLICATIONS USE MODEL EL 33 WITH 4 7K 1 4W RESISTOR Figure 2 HZM Initiating Devices Wiring Diagram Class A Style D ULC DCLA Installation Figure 3 HZM Initiating Devices Wiring Diagram Class B Style B ULC DCLB Installation DEVICE LOOP 24V...

Page 3: ... jumper J1 c Remove the 2 position plug from J1 d Reassemble the circuit board and plastic cover using the screw that was removed in the first step e Be sure to use the correct end of line device with the HZM in this configuration PB 1191 A B C D E F 1 2 3 4 5 6 7 8 9 BEAM DETECTOR WIRING CLASS B STYLE B ULC DCLB HZM J1 EARTH 3 6K 1 4W EOL RESISTOR P N 140 820185 DO NOT CONNECT MORE THAN ONE PB 11...

Page 4: ... 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9 HZM HZM HZM HZM LINE 2 LINE 1 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9 HZM HZM HZM HZM LINE 2 LINE 1 NOT USED NOT USED NOT USED 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 9 HZM HZM HZM LINE 2 RETURN LINE 2 OUT LINE 1 OUT LINE 1 RETURN 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 9 HZM HZM HZM LINE 2 RETURN LINE 2 O...

Page 5: ...power connection Refer to Figure 7 for the wiring diagram 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4 4 5 5 5 5 5 6 6 6 6 6 7 7 7 7 7 8 8 8 8 8 9 9 9 9 9 HZM HZM HZM HZM HZM CLASS B INSTALLATION T TAPPING ALLOWED TO 24 VDC SEE NOTE 5 Figure 7 HZM 24 VDC Wiring Diagram Mounting 1 Mount the HZM in a standard two gang electrical box The box must have a depth of at least 3 inches 2 When the field wiring for...

Page 6: ... a t o t s m h o 5 3 e g n a R e g a t l o V y r o s i v r e p u S e v a w l l u f d e r e t l i f C D V 5 4 2 8 1 t n e r r u C e n o Z x a M A m 4 3 r e w o P C D V 4 2 e g n a R e g a t l o V C D V 2 8 2 8 8 1 t n e r r u C x a M A m 0 0 1 t n e r r u C y b d n a t S A m 6 6 p o o L C L D S F C L D t n e r r u C x a M A m 1 ELECTRICAL RATINGS ...

Page 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 8: ...y Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 034850 8 This page has been left intentionally blank Document ID A6V10233195 ...

Reviews: