Siemens HUB-4 Installation Instructions Manual Download Page 2

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-099458-9

2

-38dBm [HUB-4 to HUB-4] @ 2.5KHz), however, using conditioned data grade leased
lines from the phone company, the distance is unlimited.

Using the RS-485 Interface module, the communication distance is 12,000 feet using
18 gauge twisted pair lines.

OPERATION

On NCC WAN, the HUB-4 can communicate using either the CMI-300, MMX, NIM-1W/
NIM-1M or HUB-4 slave Modem supervising the data circuit as well as the connected
MXL or XL3 Control Panel. Each of the four independent HUB-4 channels provides the
means to transmit data to and from the XLS, MXL or XL3 and the NCC WAN Head-End
System. The HUB-4 can also communicate with up to 16 WAIO cards, supervising the
data circuit for them as well as their inputs. Each of the four independent HUB-4
channels provides the means to transmit data to and from the WAIOs and the NCC
WAN head end system. In addition, the HUB-4 can support FSI protocol to communi-
cate to an MXL using a NIM-1W or to an XLS using a HUB-4 slave so that an NCC or a
Desigo CC via the PMI-2 Concentrator will act as the remote management system.
Similarly, the HUB-4 can support FSI protocol to an RPM in an XLS fire system.

The HUB-4 Card is divided into five main sections: four external link sections and a
control section.  The control section provides supervision of the HNET data channel
(Connection to the NCC WAN/PMI-2 Concentrator) and receives data from each of the
external links for transmission to the NCC WAN/PMI-2 Concentrator. The control
section also provides on board processor and integrity supervision. When installed in
the XLS system, the HUB-4 operates in slave mode.

Controls and Indicators

The front panel of the HUB-4 contains one reset switch, 15 LEDs and three HNET
address switches as shown in Figure 1.

A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the HUB-4 operation.

The LEDs follow the reset switch and their functions are defined as follows:

POWER

(Green)

Normally ON. When illuminated, indicates that power
for the HUB-4 is applied to the card.

CARD FAIL

(Yellow)

Normally OFF. When illuminated, indicates that the
card microprocessor has failed. May illuminate for 2-4
seconds when initially powered.

HNET FAIL

(Yellow)

When consistantly illuminated, the HUB-4 has de-
tected an HNET loss of supervision of the NCC. When
the HUB-4 detects an HNET failure, it will cause all
configured ports to shut down communication to
remote units.  The muted ports will be indicated by a
flashing OPEN/SHORT LED. When flashing rapidly, the
HUB-4 has been addressed via the front panel HNET
address select switches with an inappropriate address,
i.e., address zero, or addressed above 252 decimal.

PORTS 1 – 4

The LEDs for each independent modem block module
or RS-485 Interface module are referred to as ports.
When all three LEDs are flashing for a specific port,

Summary of Contents for HUB-4

Page 1: ...a l C 7 e l y t S 3 L X A N A N X M M X M M N A W C C N y l n o L X M A N A N 0 0 3 I M C 0 0 3 I M C L X M I S F W 1 M I N A N d n a M 1 W 1 M I N k c o l B m e d o M A N r o N A W C C N 2 I M P r o t a r t n e c n o C S L X I S F M P R B U H B U H B U H A N r e h t O s O I A W 6 1 1 s O I A W 6 1 1 A N A N N A W C C N y l n o Each of the four data channels is controlled by a separate micro contr...

Page 2: ... of the HNET data channel Connection to the NCC WAN PMI 2 Concentrator and receives data from each of the external links for transmission to the NCC WAN PMI 2 Concentrator The control section also provides on board processor and integrity supervision When installed in the XLS system the HUB 4 operates in slave mode Controls and Indicators The front panel of the HUB 4 contains one reset switch 15 L...

Page 3: ... communications controller of the HUB 4 or loss of communications between the HUB 4 and the remote fire system Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the HUB 4 PRE INSTALLATION Switch and Jumper Settings are required only on HUB 4 Main 2 and HUB 4 COM 2 boards that are not factory preassembled 1 Network Address Switches Set the three...

Page 4: ...e c a f r e t n I 5 8 4 S R 1 r o k c o l B m e d o M 1 2 M O C 4 B U H 1 2 n i a M 4 B U H 1 2 s e l u d o M e c a f r e t n I 5 8 4 S R 2 r o s k c o l B m e d o M 2 2 M O C 4 B U H 1 2 n i a M 4 B U H 1 3 e c a f r e t n I 5 8 4 S R 1 d n a s k c o l B m e d o M 2 r o s k c o l B m e d o M 3 2 M O C 4 B U H 2 2 n i a M 4 B U H 1 s e l u d o M e c a f e t n I 5 8 4 S R 3 r o s e l u d o M e c a ...

Page 5: ...HUB 4 Main 2 and secure them in place Refer to Figure 5 page 6 8 If a second HUB 4 COM 2 is required install it now by following the previous steps When installing Modem Block or RS 485 Interface modules refer toTable 4 for correct placement on HUB 4 Main 2 9 Connect the Modem Block or RS 485 Interface module to the HUB 4 COM 2 by lining up the 2x10 connector on the Modem Block or RS 485 Interface...

Page 6: ...c o l B m e d o M d n o c e s e c a l P 2 M O C 4 B U H d n o c e s f o 1 P n o e l u d o M e c a f r e t n I 5 8 4 S R r o k c o l B m e d o M d r i h t e c a l P 1 2 3 4 2 n i a M 4 B U H f o 1 P n o 2 M O C 4 B U H t s r i f e c a l P 2 n i a M 4 B U H f o 3 P n o 2 M O C 4 B U H d n o c e s e c a l P 2 M O C 4 B U H t s r i f f o 1 P n o e l u d o M e c a f r e t n I 5 8 4 S R r o k c o l B m ...

Page 7: ...e card in until the card edge connectors contact the receptacles on the motherboard MODEM BLOCK MODULE JUMPER SETTINGS The Modem Block module has three configuration jumpers JP1 JP2 and JP3 Refer to Figure 7 for the location of the jumpers Set the jumpers to the configuration shown in Table 5 Refer to the Modem Block Installation Instructions P N 315 099356 for further information J2 RS485 INTERFA...

Page 8: ...card cage slot in which it is installed To Connect External Wiring 1 Loosen the screw of the terminal by turning it counterclockwise 2 Insert the wire into the side of the terminal block 3 Tighten the screw of the terminal block by turning it clockwise The HUB 4 can be connected in three ways Refer to Figures 7 11 As a single supervised Style 4 connection As a linked supervised Style 7 connection ...

Page 9: ... 20 AWG 5 miles max 22 AWG 3 miles max 0 6 μF max line to line 560 OHM EOL P N 140 988066 Figure 9 Typical Class B Style 4 HUB 4 Wiring Connection to CMI 300 on MXL ELECTRICAL RATINGS Input Power 24V Back Plane Current 0 Screw Terminal 24V Current 400mA 6 2V Back Plane Current 30mA 24V Standby Current 400mA Output Power Each modem 2V peak to peak max Channel pair 1 3mA max Maximum line attenuation...

Page 10: ...M 3 MODEM 2 MODEM 4 ONE SLOT OF CC 5 WITH HUB 4 INSTALLED GND FAULT 24V 12A FAIL 24V 4A FAIL MODULE FAIL HNET FAIL CAN FAIL RESET POWER PSC 12 _ NON POWER LIMITED OUTPUT 24VDC 12A Max CMI 300 _ BATTERY TB4 OFF O ON TB2 P9 P12 ONES TENS HUNDREDS HNET Figure 10 Typical Class A Style 7 HUB 4 Wiring Connection to CMI 300 on MXL NOTES 1 Mount the LLM 1 within the MXL enclosure Refer to the LLM 1 Instal...

Page 11: ... 5 pins 1 16 3 14 18 AWG 8 miles max 20 AWG 5 miles max 22 AWG 3 miles max 0 6 μF max line to line MMX 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 A A A A B B B B B B B B A A A A 17 18 19 20 21 22 23 24 MODEM 3 MODEM 2 MODEM 4 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND FAULT 24V 12A FAIL 24V 4A FAIL MODULE FAIL HNET FAIL CAN FAIL RESET POWER PSC 12 1 _ _ 2 TB2 ...

Page 12: ...1 12 11 10 9 8 7 6 5 4 3 2 1 WAIO TB2 TB1 MODEM OR RS 485 INTERFACE 4 TO PSC 12 TB4 TO PSC 12 TB4 MODEM OR RS 485 INTERFACE 2 120 OHMS EOLR TERMINATION RESISTORS 2 1 INPUT TERMINALS ON NEXT WAIO 1 2 3 4 1 2 3 4 TB1 TB2 LLM 1 5 6 TO ADDITIONAL WAIOs MAX 16 TERMINATE LAST WAIO WITH 120 OHM RESISTOR ON TERMINALS 3 4 AND 5 6 120 OHMS EOLR Figure 12 Typical Class B Style 4 Wiring to WAIO Connection NOT...

Page 13: ...If only one interface is used on a COM 2 card it must be placed on Port 1 or Port 3 NCC WAN PMI 2 CONCENTRATOR Figure 14 Style 4 Wiring Between HUB 4 s with RS 485 interface or Modem Block Figure 15 Style 7 Wiring Between HUB 4 s with RS 485 interface 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED A A A A B B B B A A B B 1 2 3 4 5 6 7 8 9 10 ...

Page 14: ...er NEC 760 5K 5 1 16 x The interface type Modem or RS 485 must match on each COM 2 card If only one interface is used on a COM 2 card it must be placed on Port 1 or Port 3 NCC WAN PMI 2 CONCENTRATOR Figure 16 Style 4 Wiring Between HUB 4 s with RS 485 interface to RPM 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ONE SLOT OF CC 5 1 WITH HUB 4 INSTALLED A A A A B B B B A A ...

Page 15: ... 2 4 Refer to NIM 1M instructions P N 315 099105 configuration settings and specific wiring guidelines NIM 1M Module Board The LLM 1 inserts 10 ohms between TB1 and TB2 terminals 2 and 3 20 ohms total 5 Install the LLM 1 in the MXL enclosure 2 Modem Ratings 14 18 AWG 10 miles Max 20 AWG 6 miles Max 22 AWG 4 miles Max 0 8 uf max line to line 14 22 AWG unshielded twisted pair x x x The interface typ...

Page 16: ...g Technologies Division Florham Park NJ Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada P N 315 099458 9 THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK Document ID A6V10233204 ...

Reviews: