WIRING

(Refer to Figure 3.) Refer to the wiring diagram and wire the addressable interface
module accordingly.

Recommended wire size:

18 AWG minimum
14 AWG maximum

NOTES:
1.

All supervised switches must be held closed and/or open for at least a quarter of a second to guarantee detection.

2. End of line device: 470 ohm, 1/4W resistor, P/N 140-820164. For Canadian applications, use Model EL-33 with 470 ohm, 1/4W resistor.
3. HTRI-M is polarity insensitive. Line 1 and Line 2 can be either line of the loop.
4. The supervised switches have the following ratings:

Voltage maximum:

27 VDC

Current maximum:

6mA during polling

Contact  resistance  maximum: 10 ohms
Maximum cable length:

200 feet (18 AWG)

C

Line to line

: 0.02uF

C

Line to shield

: 0.04uF

Max line size:  14 AWG

Min line size:  18 AWG

Ground shield ONLY at the specified location on the Control Panel.

EOL device must be a 470 ohm, 1/4 W resistor.

When replacing an existing  HTRI on a device loop,

you must also replace the EOL resistor if it is not

470 ohms, 1/4W.

5. The green wire must be connected to earth ground.

a. Use wire nuts to pass the shield wire through the electrical box with 

NO

 connection to the device green wire.

b. Use shielded wire to connect the switch wiring.
c. Tie the switch wiring shield to earth ground.

6. For proprietary burglary application:

a. Use a TSW-1/2 tamper switch to monitor the main enclosure.
b. Monitor each HTRI-M related to this application continuously by using a listed motion detector (to prevent tampering).

7. In supervisory:  HTRI-M draws 1.3mA
8. All circuits are power limited.
9. Positive and negative ground fault detected at <25K ohms for orange terminals.

MOUNTING

The Model HTRI-M mounts directly into a single gang switchbox
(user supplied)

Connect the appropriate wires using wire
nuts.Tuck the HTRI-M module inside the
electrical box and dress the wiring as re-
quired. (See Figure 4.)

BLACK

GREEN

ORANGE

ORANGE

LINE 2

LINE 2

LINE 1

LINE 1

HTRI-M

RED

TO NEXT

ADDRESSABLE DEVICE

GROUND

(SEE NOTE 5)

470 OHM, ¼W

END OF LINE DEVICE

(SEE NOTE 2)

SUPERVISED SWITCH

(SEE NOTES 1 AND 2)

FROM FIREFINDER-XLS / FS-250

CONTROL PANEL ADDRESSABLE

LOOP DRIVER CIRCUIT OR FROM

PREVIOUS ADDRESSABLE DEVICE

Figure 4

Mounting the HTRI-M

SINGLEGANG

SWITCHBOX

(USER SUPPLIED)

DO NOT

USE REAR

CONDUIT

ENTRY

BLANK SINGLEGANG

SWITCHPLATE

(USER SUPPLIED)

ORG

BLK

GRN

ORG

RED

ALL

CONNECTIONS

ARE

POWER

LIMITED

EAR

TH

GND

LINE
2

LIN

E

1

HTRI-M

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

P/N 315-049480-4

ELECTRICAL RATINGS

p

o

o

L

C

L

D

-

S

F

/

C

L

D

t

n

e

r

r

u

C

.

x

a

M

A

m

3

.

1

Figure 3

Installing the HTRI-M Wiring