P/N 315-049480-4

Figure 1

HTRI-M Module

The Model HTRI-M Series Addressable Interface
Module from Siemens Industry, Inc. interfaces
direct shorting devices to the DLC loop circuit of
the FireFinder-XLS System or the FS-DLC loop of
the FS-250 System. It is also approved for 1076,
Proprietary Burglary.

The HTRI-M can monitor a normally open or closed
dry contact and it can report the status of the contact.

PROGRAMMING

Refer to Figure 1 to locate the red and black DLC/FS-DLC loop circuit wires of the HTRI-M.

Connect the Addressable Loop Driver circuit wires of the HTRI-M to the Model DPU
Programmer/Tester. Use the cable provided with the Programmer/Tester and the 2
alligator clip to banana plug adapters provided.

To Prevent Damage To The DPU:

DO NOT connect a HTRI-M to the DPU until all field wiring is removed from the

red and black DLC/FS-DLC loop circuit wires of the HTRI-M.

Connection from the DPU to the HTRI-M is not polarity sensitive. Refer to Figure

3 for the proper connections to the control panel.

(Refer to Figure 2.) Follow the instructions in the 

DPU Programmer/Tester Manual

(P/N 315-033260) to program the desired address into HTRI-M.

Record the device address on the label located on the HTRI-M. The HTRI-M can now
be installed and wired to the system.

ORG

BLK

LINE

2

LINE

1

GRN

ORG

RED

ALL CONNECTIONS

ARE POWER

LIMITED

EARTH

GND

HTRI-M

Addressable Interface Module

Installation Instructions
Model HTRI-M

NOTES:

1. There can be any number of normally closed or normally open switches.
2. The end of line resistor must be located at the last switch.
3. Do not wire a normally closed switch across the end of line resistor.
4. Only for use with security and status applications.
5. Do not use N.O. switches for security applications.

Figure 2

Wiring Switches

NORMALLY OPEN

SWITCHES

(SEE NOTES 2, 3 AND 5)

PROGRAMMABLE

NORMALLY CLOSED

SWITCHES

(SEE NOTE 4)

PROGRAMMABLE

END OF LINE

RESISTOR

470 OHMS,

1/4W

END OF LINE

RESISTOR

470 OHMS,

1/4W